Steril-Aire Enhanced UVC Kit Скачать руководство пользователя страница 2

 

 
 

 

 

I

NSTALLATION 

&

 

O

PERATION

 

 

 

  NOTE:

  Ensure  that  Emitter  is  installed  before 

power  is  applied.  Installing  Emitter  after  power  has 
been  applied may  trigger  the 

“end-of-lamp-life circuit” 

and the  Emitter  may  fail to  light. If  this  happens,  shut 
off power for 10 seconds and  then turn power back  on. 
Emitter will then light.. 

 

 

CAUTION:

  Do  not  drill  into  coil,  refrigerant lines 

or  other  mechanical  equipment.  Consult  all  applicable 
codes  before  installing.  Check  power  supply  housing 
label for  the  correct  power  requirements. Obtain power 
from  a  suitable,  protected  (fused) and grounded power 
source. 

 

The  Enhanced  UVC  Kit  is  comprised  of  the  following 
components:

  

 

A  Power  Supply  with  an  M12  Recepticle,  A  3  foot 
Emitter  Connection  Cable  (with  an  IP67  Connector  & 
M12 plug), and two Spring Clips. 

 

 

Emitters are not included but sold separately 

 

 

INSTALLATION SPECIFICATIONS 

 
The  Enhanced  UVC  Kit  is  installed  downstream  from 
the  coil.  If  downstream  space  is  unavailable,  install 
upstream.  
 
The  Emitter  should  be  at  least 

1”  away  from  any 

heating coil and not make contact with the AHU blower. 
 

 
 
 
 
 
 
 
 
 
 

 

INSTALLATION INSTRUCTIONS 

 

WARNING

Before  performing  maintenance  or 

service  on  fixture,  ensure  unit  is  unplugged. 
Electrical shock can cause injury or death. 

 

1. 

The  Emitter  access  door  or  panel  should  be 
interlocked (interlock switch P/N 

90000120)

 with 

the power source to turn Emitter(s) off when the 
Air  Handler  is  opened.  It  should  have  signs 
(provided) alerting maintenance personnel to the 
possible hazard of looking at or exposing skin to 
UVC  energy.  Service  accesses  may  be 
equipped with a glass or Lexan

® 

window to view 

Emitters;  viewports  are  available  as  an 
accessory.    UVC  energy  does  not  penetrate 
common glass or Lexan

®

.

 

 

2.  If applicable, remove outer cover of air handler.  

 

3.

 

UVC  energy  may  damage  some  plastics.  Wrap 
suspect  items  with  aluminum  tape;  use  metallic 
conduit or use other appropriate shielding where 
these items may be in "line of sight" of the UVC 
energy. 

 

4.    Determine  an  appropriate  flat-surfaced  location 

for mounting  the  power  supply.    Make  sure  that 
the  Emitter  Connection  Cable  (with  extension 
cord,  if  applicable)  can  reach  the  pins  of  the 
Emitter  and  that  M12  Plug  can  reach  the  M12 
Recepticle  at  the  power  source;  mount  the 
power  supply.    The  recommended  maximum 
extension  wire  length  from  Emitter  to  power 
supply is 3

5’ (10.67m).  

 

5.  If  using  the  Spring  C-Clips,  mount  the  two  (2) 

spring  C-clips  on  an  existing  panel  or  framing 
structure  facing  the  coil.    The  clips  should  be 
attached  to  the  Emitter  on  both  ceramic  ends. 
Install  Emitter  ceramic  into  the  spring  clips 
provided. 
 

 

 

Содержание Enhanced UVC Kit

Страница 1: ... Emitter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted UVC Emitters are fragile To prevent accidental breakage handle the UVC Emitter with care Voltages outside of the range designed for the unit will void the warranty and do permanent damage to the entire unit Emitter contains a small quantity of mercury ...

Страница 2: ...d Electrical shock can cause injury or death 1 The Emitter access door or panel should be interlocked interlock switch P N 90000120 with the power source to turn Emitter s off when the Air Handler is opened It should have signs provided alerting maintenance personnel to the possible hazard of looking at or exposing skin to UVC energy Service accesses may be equipped with a glass or Lexan window to...

Страница 3: ...ut Emitters should be replaced after 9000 hours of use 1 year TROUBLESHOOTING Symptom Possible Causes Corrective Action Emitter does not light Momentary loss of power Reset Power Turn off power for 10 Seconds and then turn power on Poor connection Check connection to Emitter Check wiring connections Reset Power Incorrect wiring Inspect circuit to wiring diagram Dirty pins Clean pins Reset Power Sy...

Страница 4: ...ingle Ended Emitter 21000510 EGTS 36 VO Enhanced 36 Single Ended Emitter 21000610 EGTS 42 VO Enhanced 42 Single Ended Emitter 21000910 EGTS 50 VO Enhanced 50 Single Ended Emitter 21000810 EGTS 61 VO Enhanced 61 Single Ended Emitter Replacement Parts Part Number Description 10000180 Power Supply Replacement for UVC Kit RIK 90000812 Spring Clips Kit 50000130 03 Enhanced Emitter Connection Cable 3 ft...

Отзывы: