2
I
NSTALLATION
&
O
PERATION
NOTE:
Ensure that Emitter is installed before
power is applied. Installing Emitter after power has
been applied may trigger the
“end-of-lamp-life circuit”
and the Emitter may fail to light. If this happens, shut
off power for 10 seconds and then turn power back on.
Emitter will then light..
CAUTION:
Do not drill into coil, refrigerant lines
or other mechanical equipment. Consult all applicable
codes before installing. Check power supply housing
label for the correct power requirements. Obtain power
from a suitable, protected (fused) and grounded power
source.
The Enhanced UVC Kit is comprised of the following
components:
A Power Supply with an M12 Recepticle, A 3 foot
Emitter Connection Cable (with an IP67 Connector &
M12 plug), and two Spring Clips.
Emitters are not included but sold separately
INSTALLATION SPECIFICATIONS
The Enhanced UVC Kit is installed downstream from
the coil. If downstream space is unavailable, install
upstream.
The Emitter should be at least
1” away from any
heating coil and not make contact with the AHU blower.
INSTALLATION INSTRUCTIONS
WARNING
:
Before performing maintenance or
service on fixture, ensure unit is unplugged.
Electrical shock can cause injury or death.
1.
The Emitter access door or panel should be
interlocked (interlock switch P/N
90000120)
with
the power source to turn Emitter(s) off when the
Air Handler is opened. It should have signs
(provided) alerting maintenance personnel to the
possible hazard of looking at or exposing skin to
UVC energy. Service accesses may be
equipped with a glass or Lexan
®
window to view
Emitters; viewports are available as an
accessory. UVC energy does not penetrate
common glass or Lexan
®
.
2. If applicable, remove outer cover of air handler.
3.
UVC energy may damage some plastics. Wrap
suspect items with aluminum tape; use metallic
conduit or use other appropriate shielding where
these items may be in "line of sight" of the UVC
energy.
4. Determine an appropriate flat-surfaced location
for mounting the power supply. Make sure that
the Emitter Connection Cable (with extension
cord, if applicable) can reach the pins of the
Emitter and that M12 Plug can reach the M12
Recepticle at the power source; mount the
power supply. The recommended maximum
extension wire length from Emitter to power
supply is 3
5’ (10.67m).
5. If using the Spring C-Clips, mount the two (2)
spring C-clips on an existing panel or framing
structure facing the coil. The clips should be
attached to the Emitter on both ceramic ends.
Install Emitter ceramic into the spring clips
provided.