READING THE DISPLAY
Normal Run: Indicates that
Emitters are lit and There are
no alarm conditions
Emitters Off: A flashing run light
Indicates that the emitters are
turned off.
Bank Faults: These alarms indicate that an
emitter or power supply may need attention.
Cycling the emitters power off/on or a reset will
clear the alarm.
Bank Over Current: Fast flashing bank lights indicates that one or more banks are drawing
more current than the watchdog was designed for.
Replace Emitters: Both bank lights flashing every second indicates that the emitters have reached
the end of their useful lifespan. The 9,000-hour timer runs only when power is applied to the
emitters. Replace with authentic Steril-Aire emitters for maximum output and lifespan. Blinks once
every second.
MENU DISPLAYS AND FUNCTIONS
Display a menu by clicking the reset button. Select the desired menu by clicking through the menus. If you missed your
menu, keep clicking until your menu is displayed again. If you wait long enough, the menu will time out and normal operation
will resume. Once the desired menu is displayed, press and hold the reset button until the menu display changes.
Menu 0: Reset Emitter Fault: Use the reset emitter fault by holding the reset button down or cycle
through the menu. A successful reset will be followed by a marque pattern of LED’s. This pattern
will repeat itself 8 times.
Menu 1: Report Run Hours: This is part of the 9,000-hour timer. Hold the reset button until the
green run LED starts to flash. Each flash of the LED indicated that 1,000-hours has expired. At
9,000-hours, the end of emitter life alarm will flash. This function will keep counting even after
9,000-hours has expired.
Menu 2: This menu is reserved and has no function at this time.
Menu 3: Reset 9,000 Hour Timer: This menu resets the runtime timer. It will clear the 9,000-hour
timer after emitters have been replaced by installing authentic Steril-Aire emitters for maximum
output and lifespan. Hold the reset button until the display normal run status.
Emitters Off.
No Alarm.
Bank 1 Off
Run Flashing
Bank 2 Off
Bank 1 Fault.
BMS Alarm
Bank 1 On
Run Off
Bank 2 Off
Bank 2 Fault.
BMS Alarm
Bank 1 Off
Run Off
Bank 2 On
Bank 1 & 2 Fault.
BMS Alarm
Bank 1 On
Run Off
Bank 2 On
Bank 1 & 2 Over Current.
BMS Alarm
Bank 1 Flashing
Run On
Bank 2 Flashing
Replace Emitters.
No Alarm
Bank 1 Blink
Run Blink
Bank 2 Blink
Menu 0
Reset
Bank 1 Off
Run Off
Bank 2 Off
Menu 1
Report Run Hours
Bank 1 On
Run Off
Bank 2 Off
Menu 2
Not Assigned
Bank 1 On
Run On
Bank 2 Off
Menu 3
Reset 9K timer
Bank 1 On
Run On
Bank 2 On
Normal Run.
No Alarm.
Bank 1 Off
Run On
Bank 2 Off