Stelpro SEFECM Series Скачать руководство пользователя страница 4

4

INSSEFECMI0513

12''

305mm

MINIMUM

12''

305mm

MINIMUM

36''

914mm

MINIMUM

DETAIL A

1/2''

13mm

DO NOT POSITION

THE SENSOR IN

THIS AREA

FURNACE

DRILL

DuCTs AnD fiLTers

Ducts must be designed to deliver the correct airflow at the specified external static pressure . You should insulate the ducts crossing non-heated 

areas. Moreover, use flexible return and supply connectors in order to avoid vibrations as much as possible. To make your furnace even quieter, 

follow these instructions:
1. Cover the vertical return and supply ducts with soundproofing material;
2. Install at most one or two elbows between registers and the return and supply connectors;
3. Install flexible hangers to suspend the ducts;
4. Install baffles in elbows with a small curvature radius.
All “SEFECM” series models are equipped with a filter rack (including the filter) that you will find on top of the furnace. You can install this rack on 

one of the three external sides of the furnace or at its bottom. Using snips, cut the selected rack opening following the slots and holes, and screw 

the filter rack on it. 

PLenum TemPerATure ConTroL PoTenTiomeTer

When you install the plenum temperature sensor, you can select the plenum temperature set point with a potentiometer installed on the control 

card. The default factory set point is 60°C (140°F). You can select the set point from a temperature range between 40°C (104°F) and 70°C (158°F).

oPTionAL ACCessories

The furnace is equipped with all the devices required for the addition of an air-conditioner or a heat pump (except the heat-cool thermostat). The 

refrigerant and drainage pipes must be installed either in the furnace supply or return duct and should not prevent you from removing the door in 

front of the furnace.
You can also install a thermostat with an outdoor sensor or a two-stage thermostat to control your furnace. To do so, you must refer to the 

instructions supplied with the thermostat (see also the illustrations on following page) as well as the furnace wiring diagram.
When the electric furnace is used in combination with a wood heating unit, you must connect the thermostat of the wood heating unit across low 

voltage terminals R and G of the furnace. This thermostat will automatically turn the blower of the furnace on.

N.B. please note that if one of these accessories is installed, you must refer to the appropriate guide.

PLenum TemPerATure sensor

A plenum temperature sensor is included with the furnace. It is up to you to install it or not. However, if you choose to not install the sensor, you 

must disconnect it from the control card. The furnace will operate even if the sensor is not connected (see the OPERATION section). You can 

use the plenum temperature regulation function if you install the sensor and you connect it to the control card. This function is explained in the 

OPERATION section. Refer to the illustration below to properly install the plenum temperature sensor.

Содержание SEFECM Series

Страница 1: ...r further information or to consult this guide online please visit our website at www stelpro com This unit complies with CSA and UL standards This unit is approved according to the Canadian and Ameri...

Страница 2: ...ouch hot surfaces Let the unit cool down for a few minutes before handling it it stays warm for some time after shut down Never block air vents This obstruction could lead to overheating which could r...

Страница 3: ...tion Location You must install the furnace on a dry and solid base in an area free of flammable liquids or vapors and combustible materials You must indicate to the furnace user the location of the sw...

Страница 4: ...e between 40 C 104 F and 70 C 158 F Optional accessories The furnace is equipped with all the devices required for the addition of an air conditioner or a heat pump except the heat cool thermostat The...

Страница 5: ...rnace at 208 VAC you must change a connection on the 24 V terminal board of the transformer see the illustration below Refer to the local and national electrical codes to know which wire size fuses an...

Страница 6: ...t or heat of the sun a lamp a fireplace or any other heat source close or in front of an air outlet close to concealed ducts or a chimney and in a location with poor air flow e g behind a door or with...

Страница 7: ...EATING button provides the selection of the 5 kW continuous heating mode 8 5 kW CONTINUOUS HEATING pilot light indicates that the 5 kW continuous heating mode is activated This mode is pending if the...

Страница 8: ...tivate the 100 capacity Continuous ventilation Two ventilation speeds can be selected on the furnace control panel Low speed continuous ventilation or High speed continuous ventilation If the pilot li...

Страница 9: ...r conditioning A potentiometer allowing to adjust the airflow corresponds to each of these five modes The potentiometers are located in front of the furnace electrical panel The adjustment scales of t...

Страница 10: ...at is set off This means that there is a risk of electric shock as long as the unit is energized Preventive maintenance Do not try to repair your furnace yourself Call a qualified technician However b...

Страница 11: ...the unit capacity Faulty relay Control card autodiagnostic The control card of the furnace is equipped with three LED pilot lights that allow easy and quick diagnostic of its essential functions They...

Страница 12: ...SEFECM2021 9 CIR 003 SEFECM2321 MAIN CONTROL CARD SEFECM2321 9 CIR 003 SEFECM2721 MAIN CONTROL CARD SEFECM2721 9 CIR 003 SEFECM3021 MAIN CONTROL CARD SEFECM3021 10 CIR 005 SEFECM1021 CONTROL CIRCUIT B...

Страница 13: ...y for property or personal injury damages penalties special or punitive damages damages for lost profits loss of use of equipment cost of capital cost of substitute products facilities or services shu...

Страница 14: ......

Отзывы: