Installation InstructionsWireless High Bay Controls
English
IoT
E
N
AB
LE
D BY
Страница 1: ...RoHS Compliant HBS DC HBS 300 HBS 200 HBS 200 HBS 300 HBS DC Installation Instructions Wireless High Bay Controls English I o T E N A B L ED BY ...
Страница 2: ...bay aisle ways where aisle coverage and wireless control is desired Package Contents Installation Overview WARNING Turn power off at the circuit breaker before installing the sensor Sensor must be installed and used in accordance with appropriate electrical codes and regulations Installation by a qualified electrician is recommended Communication Frequency Transmission Range 2 4 GHz 600 ft 182 8 m...
Страница 3: ... 62 in 15 75 mm Product description Product description Specifications Specifications The HBS 200 High Bay Occupancy Sensor provides occupancy based lighting control in high bay applications and communicates wirelessly to other devices to create groups lighting zones The sensor contains two dual element pyroelectric detectors and is engineered to perform at a wide range of mounting heights up to 4...
Страница 4: ...just snaps into the connection terminal No tools are required This sensor is commissioned remotely through the EnergyCenter software Product description The HBS DC Wireless Control Module works with STEINEL s HBS 200 and HBS 300 wireless lighting control devices to create control zones without the need for additional wiring The HBS DC typically comes preinstalled in the STEINEL wireless device Dev...
Страница 5: ... on a stable platform EM 1 Fixture HBS Sensor Junction box mounting HBS 300 HBS 200 Wiring HBS 300 HBS 200 When installing make sure power has been switched off at the breaker and check that the circuit is dead with a voltage tester The leads consist of three wires Black line White neutral Red load When the HBS DC is installed Violet DIM Gray DIM If in doubt identify the individual conductors with...
Страница 6: ... load will turn ON for up to one minute If no motion is detected the load will switch OFF If motion is detected and the target light level setting is less than the daylight level the load will stay ON for the selected time delay setting per DIP switch setting If the daylight level at power up is greater than the target light level setting the load will switch OFF regardless of occupancy Surge prot...
Страница 7: ...200 can be rotated 90 degrees To do this remove the sensor housing from the back box by pressing the tabs on either side of the sensor Coverage may vary depending on mounting height and environmental conditions 10 20 30 40 LC3 40 ft 50 50 40 40 35 ft 22 ft 22 ft 35 ft 10 20 30 40 Aisle LC3 radial tangential 40 ft 13 ft 50 ft 53 ft 53 ft 50 ft Setup Commissioning Lens Covers Lens covers can be used...
Страница 8: ...pment should be installed and operated with a minimum distance of 20 centimeters between the radiator and your body Troubleshooting Wireless communication troubleshooting Is the receiver device too far away from the transmitting device resulting in too weak of a signal at the receiver See Transmission Range on page 3 Can the radio signal leave the transmitter and reach the receiver or is it inhibi...
Страница 9: ...1 Lyndale Avenue South USA Bloomington MN 55420 Tel 1 952 888 5950 Fax 1 952 888 5132 www steinel net Autani LLC 7090 Columbia Gateway Drive Suite 140 Columbia MD 21046 Tel 1 443 320 2233 www autani com I o T E N A B L ED BY ...