background image

- 20 -

- 21 -

The True Presence function is not 

available, the sensor functions as a 

conventional presence detector.

Scenario 1:

Very noisy environments, heavy industry

 

– As scenario 2, but with a further  

reduced sensitivity. 

 

7.  Maintenance and care

The product requires no maintenance.

The sensor can be cleaned with a damp 

cloth (without detergents) if dirty. 

8.  Troubleshooting

No connection with the sensor.

 

– Break in network cable or network 

cable not connected.

•  Check cabling.

 

– No PoE injector installed, or the 

network switch being used does not 

support PoE.

•  Check PoE supply.

 

– IP address incorrectly configured.

•  Check network settings. 

•  It may be necessary to reset via 

Smart Remote app and re-connect 

with standard configuration.

 

– Firewall preventing communication.

•  Check firewall settings.

Sensor sending a motion detection 

signal when it should not.

 

– There is interference, e.g. fan, air-con-

ditioning system or other moving 

parts, in the detection zone

•  Adjust detection zone or fit 

shrouds, increase distance.

 

– Animals are moving in detection zone.

•  Adjust zone or fit shrouds.

 

– Persons are being detected in adja-

cent rooms through thin walls.

•  Reduce sensor reach. 

 

– Wind is moving paper or plants in the 

detection zone.

•  Change detection zone.

 

– Sensor near Wi-Fi or other wireless 

communication source.

•  Install at least 2 m away from the 

wireless communication source.

Sensor not responding to movement 

quickly enough.

 

– Distance from sensor too far.

•  Install additional sensors.

•  Optimise sensor positioning.

 

– Reach setting insufficient

•  Adjust reach.

Temperature level inexact.

 

– Calibration required.

•  Enter correction factor via sensor 

settings.

Sensor not connecting with the app.

 

– App or smartphone system crash.

•  Restart mobile terminal device. 

 

9.  Disposal

Electrical and electronic equipment, acces-

sories and packaging must be recycled in 

an environmentally compatible manner.

 

 Do not dispose of electrical 

and electronic equipment as 

domestic waste.

EU countries only

Under the current European Directive on 

Waste Electrical and Electronic Equip-

ment and its implementation in national 

law, electrical and electronic equipment 

no longer suitable for use must be 

collected separately and recycled in an 

environmentally compatible manner.

A customised IP or a DHCP client can be 

set up via the web interface.

User code: 

updwd123

Administrator code: 

adm123

Setting Hallway IP detection

Reach can be set separately for both 

directions via Smart Remote app The 

Steinel logo on the sensor indicates the 

direction. 

(Fig. 6.1)

a   

The reach shown by "S" points to the 

direction in which the S in the Steinel 

logo points.

b  

The reach shown by "L" points to the 

direction in which the L in the Steinel 

logo points.

•  Setting reach via:

 

Smart Remote app

 

Web interface

 

IP interface 

Setting HF 360-2 IP detection

The reach can be set digitally or man-

ually. 

•  Setting reach via:

 

Smart Remote app

 

Web interface

 

IP interface

•  Adjust the reach via shroud foils. 

(Fig. 6.2/6.3/6.4) 

Setting True Presence IP detection 

•  Setting reach via:

 

Smart Remote app

 

Web interface

 

IP interface

First time of using True Presence

During initial commissioning, the pres-

ence detector creates a room image.

The room must be free of movement for 

2 to 2.5 minutes for this. 

The process is completed when the 

white LED goes out.

Setting True Presence detection

The reach can be set via the  mounting 

height, radius and scenario parameters.

Scenario 9:

Small office, quiet workplace

 

– This scenario features maximum 

sensitivity. To prevent undesired 

switching, it should be used for small 

areas.

Scenario 8:

Large office, quiet workplace

 

– As scenario 9, but with a slightly 

reduced sensitivity. Also suitable for 

large areas.

Scenario 7:

Large office, large entrance area

 

– As scenario 8, but with a further  

reduced sensitivity.

Scenario 6:

Hotel room, room with persons sleeping

 

– This scenario also provides maximum 

sensitivity. In addition, signal process-

ing has been optimised to reliably de-

tect the presence of persons sleeping.

 

Scenario 5:

Hotel room, room with persons sleeping

 

– As scenario 6, but with a further  

reduced sensitivity.

Scenario 4:

Noisy workspace, light industry, hallways

 

– The sensor can be triggered by vibra-

tions. In scenarios 7-9, this may lead 

to longer stay-ON times. Scenario 4 is 

more robust in the way it works.

Scenario 3:

Noisy workspace, light industry, hallways

 

– As scenario 4, but with a further  

reduced sensitivity.

Scenario 2:

Very noisy environments, heavy industry

 

– This scenario should be used if there 

are larger vibrations or if there are 

sources of electrical interference.  

 

 

GB

Содержание Hallway IP

Страница 1: ...HF 360 2 IP Hallway IP GB DE I True Presence IP True Presence Hallway DE GB...

Страница 2: ...2 IP AP 2 x 3 5 123 mm 123 mm 57 mm 3 6 A B C D 3 7 Hallway IP UP 3 8 103 mm 68 mm 103 mm 3 9 B C D Textteil beachten Follow written instructions 3 1 HF 360 2 IP UP 2 x 3 2 103 mm 65 mm 103 mm 3 3 B...

Страница 3: ...45 mm 123 mm 3 18 A B C D 3 19 HF 360 2 IP 2 5 m 12 m 3 20 Hallway IP 2 4 m 3 m 25 m 3 21 True Presence IP 4 2 8 m 15 m 9 m 3 10 Hallway IP AP 3 11 123 mm 62 mm 123 mm 3 12 A B C D 3 13 True Presence...

Страница 4: ...6 7 4 1 4 2 4 3 A 4 4 B 4 5 5 C 5 1 Hallway IP 5 2 5 3 5 4 5 5...

Страница 5: ...8 9 6 1 a b 6 2 HF 360 2 6 3 HF 360 2 6 4 HF 360 2 5 6 5 7 5 8 5 9 6...

Страница 6: ...Verf gung gestellt und k nnen in entsprechenden Systemen weiterverar beitet werden Weiterf hrende Informationen und Doku mentation zu den einzelnen Protokollen finden Sie unter www steinel de UP Varia...

Страница 7: ...aktiv LED leuchtet blau Fehler LED leuchtet rot LAN Verbindung zum Sensor herstellen Webbrowser starten LAN Zugriff zum Sensor einrich ten Werkseinstellung IP Adresse 192 168 1 200 Der Computer muss a...

Страница 8: ...nt Reichweite des Sensors verkleinern Wind bewegt Papier oder Pflanzen im Erfassungsbereich Bereich umstellen Sensor in der N he von WLAN oder anderer Funkquelle Mindestens 2 m von der Funkquelle entf...

Страница 9: ...keine Haftung HERSTELLER 1 3 JAHR DEU GARANTIE 5 HERSTELLER GARANTIE HERSTELLER GARANTIE GB 1 About this document Please read carefully and keep in a safe place Under copyright Reproduction either in...

Страница 10: ...ault sensor IP set in the web browser True Presence reach 9 m True Presence up to a mounting height of 4 m 15 m presence 15 m movement adjustable with centimetre precision Sensor values Light measurem...

Страница 11: ...and recycled in an environmentally compatible manner A customised IP or a DHCP client can be set up via the web interface User code updwd123 Administrator code adm123 Setting Hallway IP detection Rea...

Страница 12: ...function in the proper manner and that all materials used and their surfaces are without defects Making Claims If you wish to make a claim please send your product complete and carriage paid with the...

Страница 13: ...GmbH Dieselstra e 80 84 33442 Herzebrock Clarholz Tel 49 5245 448 188 www steinel de Contact www steinel de contact 110073769 05 2021 Technische nderungen vorbehalten Subject to technical modificatio...