6.  Function and settings

Factory settings

 

– See KNX application description

 

– Test mode

Note

You will find an application description at 

knx.steinel.de

Smart Remote app

To read off the sensor values via smart-

phone or tablet, you must download the 

STEINEL Smart Remote app from your 

app store. You will need a Bluetooth- 

capable smartphone or tablet.

Android

iOS

LED function
Initialisation: 

LED flashes blue

Normal mode: 

LED OFF

Bluetooth connection active:

LED lights up blue

Error: 

LED lights up red

Programming mode: 

LED lights up 

turquoise

Hallway KNX test mode, movement:

LED permanently lights up green

Hallway KNX test mode, no move-

ment:

 LED permanently lights up red

Activating functions

Activating with ETS tool via the "General 

settings" window.

Issue physical address.

•  Generate application programme in 

the ETS.

•  Load physical address and application 

programme into the sensor.

•  When prompted, press programming 

button 

D

(Fig. 4.1/4.2)

Setting Hallway KNX detection

Reach can be set separately for both 

directions. The Steinel logo on the sensor 

indicates the direction. 

(Fig. 6.1)

a  

The reach shown by "S" in the ETS 

points to the direction in which the S 

in the Steinel logo points.

b  

The reach shown by "L" in the ETS 

points to the direction in which the L 

in the Steinel logo points.

7.  Maintenance and care

The product requires no maintenance.

The sensor can be cleaned with a damp 

cloth (without detergents) if dirty.

8.  Troubleshooting

Light does not switch ON.

 

– No supply voltage.

•  Check supply voltage

 

– Switching threshold light level set too 

low.

•  Slowly increase switching threshold 

light level until light switches ON.

 

– No presence detection.

•  Ensure unobstructed sensor vision.

•  Check detection zone.

Lights do not switch OFF.

 

– Switching threshold light level too 

high.

•  Reduce switching threshold light 

level. 

 

– Stay-ON time elapsing.

•  Wait until stay-ON time elapses; 

reduce stay-ON time if necessary.

 

– Objects moving in the detection zone.

•  Check detection zone.

Sensor switches OFF despite persons 

being present.

 

– Reach set too low.

•  Change reach.

 

– Switching threshold light level too low.

•  Change switching threshold light 

level.

Sensor does not switch OFF quickly 

enough.

 

– Stay-ON time too long.

•  Reduce stay-ON time.

Sensor does not switch ON when per-

sons are present despite it being dark

 

– Switching threshold light level set too 

low.

•  Increase switching threshold light 

level.

 

– Semi-automatic mode activated.

•  Activate fully automatic mode or 

switch light ON at button.

 

–  4 hours OFF activated.

•  Deactivate 4 hours OFF

Sensor switches ON despite no per-

sons being present.

 

– Movement within adjacent rooms and 

floor levels.

•  Change reach

•  Reducer sensitivity.

Wrong temperature indicated.

 

– Different layers of air.

•  Enter correction factor into the ETS. 

 

9.  Disposal

Electrical and electronic equipment, acces-

sories and packaging must be recycled in 

an environmentally compatible manner.

   Do not dispose of electrical 

and electronic equipment as 

domestic waste.

EU countries only

Under the current European Directive on 

Waste Electrical and Electronic Equip-

ment and its implementation in national 

law, electrical and electronic equipment 

no longer suitable for use must be 

collected separately and recycled in an 

environmentally compatible manner.

10. Conformity

STEINEL Vertrieb GmbH hereby declares 

that the True Presence COM1/COM2 / 

Hallway COM1/COM2 radio equipment 

type conforms to Directive 2014/53/EU. 

The full wording of the EU Declaration of 

Conformity is available for downloading 

from the following Internet address: 

www.steinel.de

Содержание 4007841058036

Страница 1: ...e 80 84 33442 Herzebrock Clarholz Tel 49 5245 448 188 www steinel de Contact www steinel de contact 110073767 10 2020 Technische nderungen vorbehalten Subject to technical modification without notice...

Страница 2: ...3 Textteil beachten Follow written instructions 3 1 HF 360 2 KNX UP 3 2 103 103 60 3 3 B C E D DE 7 GB 12 3 4 HF 360 2 KNX AP 3 5 123 123 57 3 6 A B C E D 3 7 Hallway KNX UP 3 8 103 103 66 5 3 9 B C E...

Страница 3: ...4 5 3 10 Hallway KNX AP 3 11 123 123 62 3 12 A B C E D 3 13 HF 360 2 KNX 2 5 m 12 m 3 14 Hallway KNX 4 2 4 m 25 m 3 m 4 1 LED Prog D I O 4 2 D I O 5 5 1 Hallway KNX 5 2 5 3 5 4 I O...

Страница 4: ...hrt werden Nur Original Ersatzteile verwenden Reparaturen d rfen nur durch Fach werkst tten durchgef hrt werden 3 HF 360 2 KNX Hallway KNX Bestimmungsgem er Gebrauch Sensor zur Deckenmontage im Innen...

Страница 5: ...Elektrischer Anschluss Anschluss Aufputz Abb 4 1 Anschluss Unterputz Abb 4 2 6 Funktion und Einstellungen Werkseinstellungen Siehe KNX Applikationsbeschreibung Testbetrieb Hinweis Die Applikationsbes...

Страница 6: ...tgeltliche Garantie gem den nachstehenden Bedingungen Wir leisten Garantie durch kostenlose Behebung der M ngel nach unserer Wahl Reparatur oder Austausch mangel hafter Teile ggf Austausch durch ein N...

Страница 7: ...3 13 Hallway KNX detection zone Fig 3 14 4 Electrical connection Surface mounted connection Fig 4 1 Concealed connection Fig 4 2 5 Installation Check all components for damage Do not use the product...

Страница 8: ...tructed sensor vision Check detection zone Lights do not switch OFF Switching threshold light level too high Reduce switching threshold light level Stay ON time elapsing Wait until stay ON time elapse...

Страница 9: ...h to make a claim please send your product complete and carriage paid with the original receipt of purchase which must show the date of purchase and product designation either to your retailer or cont...

Отзывы: