How it works / Basic function
The ultrasonic and DualTech
presence detectors from the
Control PRO range control light-
ing as well as heating, ventila-
tion and air-conditioning (COM 2
only), e.g. in offices, schools,
public buildings or at home, in
relation to ambient light level
and the presence of persons.
The presence detector's switch-
ing outputs and reach are set at
the potentiometers and dip
switches or by using the option-
al remote control.
Presence Control has a low in-
trinsic power consumption.
Presence Control PRO
US 360 COM1
Single US COM1
DualTech COM1
Dual US COM1
1 switching output operating in
relation to light-level setting and
presence of persons.
Settings:
- Light-level setting
- Stay-ON time, pulse mode,
IQ mode
Presence Control PRO
US 360 COM2
Single US COM2
DualTech COM2
Dual US COM2
1 switching output as COM 1.
An additional 2nd switching out-
put for operating HVAC (heating/
ventilation/air-conditioning) in re-
lation to the presence of persons.
Settings:
- Stay-ON time
- Switch-ON delay
- Room surveillance
Presence Control PRO
US 360 DIM
Single US DIM
DualTech DIM
Dual US DIM
1 switching output operating in
relation to light-level setting and
presence of persons.
Settings:
- Light-level setting
- Stay-ON time, IQ mode
- Orientation light
- Constant-lighting control
Detection zone
DualTech/US 360, mounting height 2.8 m
Single US/Dual US, mounting height 2.8 m
Single US
Dual US
PIR radial & presence detection
PIR tangential detection
US tangential & presence detection
US radial detection of substantial movements
US tangential & presence detection
US radial detection of substantial movements
DualTech
US 360
Electrical installation / Automatic mode
In selecting the wiring leads, it is
important to meet the wiring
regulations laid down in VDE
0100 (see Safety warnings on
page 19). Wiring up the pres-
ence detector: Under section 6 of
VDE 0100 520, a multiple-core
lead containing both the mains
voltage leads and the control
leads (e.g. NYM 5 x 1.52) may be
used for the wiring between sen-
sor and electronic ballast. The
mains connection lead must be
no greater than 10 mm in diame-
ter. The mains connection termi-
nal accepts 2 x 2.5 mm
2
cables.
When installing the surface-
mounting version, connect a
circuit breaker (16 A) on the line
side.
P S N
L L'
L
N
P
L
N
P S N
L L'
L
N
L
N
1-10V
1-10V
+ –
max. 100 mA
COM1
DIM
P S N
L L'
L
N
P
L
N
P S N
L L'
L
N
L
N
1-10V
1-10V
+ –
max. 100 mA
COM1
DIM
P S N
L L'
L
N
P
L
N
P S N
L L'
L
N
L
N
1-10V
1-10V
+ –
max. 100 mA
COM1
DIM
P S N
L L'
L
N
P
L
N
P S N
L L'
L
N
L
N
1-10V
1-10V
+ –
max. 100 mA
COM1
DIM
DIM
COM 1
COM 2
GB