Modular Jack
Protective
Covering
(Remove)
Multi-Conductor
Control Cable
(25 feet)
Black Plastic
Strain Relief
Clamp
Ground
Connection
Electrical
Supply Wire
208/240V
L1 & L2 Power
Connections
Steam Outlet
Safety Valve
Optional Steamist
Splitter for Two
Controls
Plug
Electrical Installation Instructions
Checklist
Models: SM-46 and SM-79
Figure 2 - Internal Electrical Connections
03/09
Pub. No. 217-J
- 2 -
Before starting, insure that the conditions of the following checklist have been met:
The proper size Steam Generator has been selected by
using the sizing page in the “Full Line Brochure,” “Pricing
Guide,” or “The Generator Sizing Guide” in the Residen-
tial Systems/Steambath Product Information section of
the Steamist website - www.steamist.com.
CAUTION: An improperly sized Steam Generator will
NOT produce the amount of steam necessary to reach
selected temperature.
The proper voltage Steam Generator has been selected
(i.e., 208V or 240V). A 208V Generator operating on
240V will damage the heating element, and a 240V
Generator operating on 208V will result in a 25%
loss of power.
The Steam Generator is installed in an upright position.
The proper sized 90°C wire and circuit breaker have
been used.
The circuit breaker is NOT a GFI (Ground Fault
Interrupter) type.
The Steam Generator is properly grounded.
The circuit breaker or disconnect switch is on.
Water supply is open to the Steam Generator.