background image

USER TRIM

Power Supply (24VDC)

Input Simulator

User trim function allows manual adjustment of the output current, this 
is  useful  for  minor  calibration  adjustment  or  trimming  out  any  sensor 
error,  ±  5%  of  range  adjustment  is  available  at  both  offset  and  span.  
Raise  and  lower  buttons  are  provided  on  the  back,  of  the  transmitter, 
accessed  using  a  3  mm  flat  blade  screw  driver.  Insert  the  screw  driver 
into  the  appropriate  slot  to  operate  the  button.  The  button  has  a  click 
action. 

METHOD
1.0 Ensure the SEM710 is correctly configured. Connect  transmitter to 
a  suitable  input  simulator  or  sensor.  Connect  output  to  a  24V  dc 
supply.    Turn  supply  on,  set  input  to  either  offset  or  span  calibration 
point. 

2.0 During normal operation the SEM710 Display reading is calculated 
from the output current drive not directly from the input, therefore the 
display may be used to monitor trim adjustment. If required the output 
current may also be monitored with a current meter.

3.0  If  the  input  falls  outside  the  ranged  output  the  SEM710  will  enter 
burnout  condition  on  the  output,  but  will  continue  to  display  the 
temperature.  The  SEM710  will  indicate  this  by  alternating  the  display 
to  show  '

OuER

'  or  '

uND

'  depending  on  the  burnout  direction  of  the 

input reading.

4.0  Trim  output  current  by  pressing  either  the  raise  or  lower  button, 
single click to step advance , or press continuously to auto advance. 
The SEM710 unit will automatically detect the correct trim point.

+

-

+

-

SEM710

The  transmitter  will  auto-
matically  detect  the  correct 
trim  point  (offset  or  span) 
based on the output current 
drive. Offset will be trimmed 
when  the  current    is  be-
tween  (3.8  to  6)  mA,    span 
when the current is between 
(18  to  22)  mA.  No  trim 
action  occurs  at  any  other 
current.

offset

span

3.8

6

18

22 

mA

 or Sensor

SUPPLY (Vs)  = (11 to 30) VDC

MAX  LOAD

Ohms  = (Vs - 11) / 0.021

OUTPUT
2 Wire (4-20) mA 
Max cable length 1000 meters
Use twisted pair cable > 30 meters

+

-

Pt100

Ø 3 mm

ELECTRICAL  INSTALLATION

Screw Driver

Shielded Cable

TC Compensation Cable

Shielded 

TURN OFF SUPPLY BEFORE   WORKING ON ANY ELECTRICAL CONNECTION

T/C

Vs

Loop 
Load

USB

+

-

3

2

1

+

-

Twisted Pair

100.0

SEM710

+

Pt100

DISPLAY

DISPLAY ERROR MESSAGES

ERR

             u 

Sensor or system error

.   (dec. pt. )               

Configuration powered by USB

OuER

   (over 105.0)   u 

Output over range (flashes actual

                  I/P measurement then Error Message)

uND

   (under -0.5)      u 

Output under range (flashes actual

                  I/P measurement then Error Message)

USB

LOWER

RAISE

+

3

2

1

-

_

INPUT CONNECTION

For cable lengths < 3 Meters shielded or twisted pair is not 
required.

For cable length  > 3 Meters and < 30 Meters  shielded or 
twisted pair is required.

Cable lengths > 30 Meters are not recommended.

Pt 100 Inputs of all three wires must be equal length 
(resistance).

T/C Inputs must use the correct compensation cable.

T/C

MECHANICAL INSTALLATION

SEM710_User_GuideUSA_5_09