IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
To maintain CE EMC requirements , input wires must be less than 30 meters.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to
supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the
place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.
ABSOLUTE MAXIMUM OPERATING CONDITIONS (To exceed may cause damage to the unit):-
Supply Voltage
± 30 VDC (Protected for over voltage and reverse connection)
Current with over voltage
± 200 mA
Input Voltage
± 5 V between any terminals
Input Current
± 100 mA between terminals 7 & 10
Ambient
Temperature (-30 to 75) °C Humidity (10 to 95) % RH (Non condensing)
SEM710 USER GUIDE
HEAD MOUNTED TRANSMITTER
UNIVERSAL TEMPERATURE INPUT
TWO WIRE (4 to 20) mA OUTPUT WITH
DISPLAY
Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.
Important - Please read this document before installing.
PRODUCT SPECIFICATION
RECEIVE AND UNPACKING
CONFIGURATION
SEM710
M-CONFIG SOFTWARE
USB CABLE
Disk or download @
www.statinst.com
COMPUTER
The following parameter can be configured by simply entering as prompted by the software
package.
· Input type (K, J, E, N, T, R, S, Pt100)
· Low range
· High range
· Units (°C, °F)
· Burnout (direction of output current on sensor burnout)
· User Trim (ON / OFF) [option to lock out trim function]
Display mode Input (°C / °F) or Output mA
Factory default:
Input type = P
Low Range = 0
High Range = 100
Units
= °C
Burnout
= UPSCALE
User Trim = ON
Display
= °C
Input
3
2
1
+
-
PT100
2 Wire (4-20) mA Output
SEM710
+
-
V
s
Loop
Load
US
B
+
-
100.0
IMPORTANT The SEM710 can be configured while connected and powered, but a portable battery powered computer must be used to avoid the effects
of ground loops.
-
Status Instruments Inc, PO Box 548, 456 Park Avenue, Scotch Plains, NJ 07076
Web Page: www.statinst.com Tel: (800) 700-3272 Fax: (800) 700-5468 email: [email protected]
Please refer to the product data sheet for full specification, available to down load at www.statinst.com.
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.
SEM710_User_GuideUSA_5_09