D2272-02-05 CN5219 SEM310 WEB User Guide
Notes
1
Any span may be selected but full accuracy is only guaranteed for spans greater than the
minimum recommended.
2
Includes the effect of calibration, linearisation and repeatability.
3
Custom characterisation is available pre-programmed at the factory. Contact your nearest
Sales office.
4
Consult Thermocouple reference tables for practical temperature ranges.
5
For supply voltages over 30V, a minimum loop load of 500
Ω
is necessary.
2.6 GENERAL
Input/Output Isolation
500 VAC
Time Constant
(Filter Off) 0.5 secs (to 90 % of final value)
Filter Factor Programmable
Off / selectable between 1 and 32 seconds / or Adaptive
Warm-up Time
2 minutes to full accuracy
ENVIRONMENTAL
Ambient Operating Range
(-40 to 85) °C
Ambient Storage Temperature
(-50 to 90) °C
Ambient Humidity Range
(10 to 95) % RH non condensing
EMC
BS EN 61326
MECHANICAL
Enclosure
DIN standard terminal block size
Material
ABS
Weight
43 g
Dimensions
44 mm diameter x 24 mm
Flammability
UL94-V0
2.7 SEM310X VERSION - FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES
2.7.1 ATEX CERTIFICATE
The SEM310X, has been issued with a EC-type examination certificate, confirming compliance with
the European ATEX directive 94/9/EC for :-
Intrinsic safety
II 1 G EEx ia IIC T4…T6.
The equipment bears the Community Mark and subject to local codes of practice, may be installed in
any of the European Economic Area (EEA) member countries. The SEM310X housing is coloured
light blue to identify the equipment as suitable for Hazardous area use. The equipment must be
installed and maintained in accordance with local requirements for electrical equipment for use in
potentially explosive atmospheres, eg EN60079-14 & EN60079-17. This instruction sheet describes
installation which conforms with BS EN60079-14 & BS EN60079-17 Electrical Installation in
Hazardous Areas. When designing systems outside the UK, the local Code of Practice should be
consulted.
Page 3
2.7.1 ATEX MARKING
COMMON INFORMATION
Manufacturer
Status Instruments Ltd
Type Number
SEM310X
CE marking
0891
Explosive Protection Marking
(Type ia) Intrinsic Safety
II 1
Equipment Group and category
G
Type of explosive atmosphere (Gas)
EEx ia IIC T4..T6
Intrinsic safety information
TRL03ATEX21013X
Certificate reference
2.7.3 SPECIAL CONDITIONS FOR SAFE USE
As indicated by the Certificate Reference "X" suffix, special conditions apply for safe use for
intrinsic safety applications. They are as follows:-
ZONES, GAS GROUPS, AND T RATING.
When connected to an approved system the SEM310X may be installed in:-
Zone 0
explosive gas air mixture continuously present
Zone 1
explosive gas air mixture likely to occur in normal use
Zone 2
explosive gas air mixture not likely to occur and if it does, it will only occur for a
short time.
Be used in gas groups;-
Group A
propane
Group B
ethylene
Group C
hydrogen
Page 4
II 1 G EEx ia IIC T4-T6. TRL 03ATEX21013X
FACTORY MUTUAL: INTRINSICALLY SAFE APPARATUS
FOR CL1,DIV1,GP ABCD T4@85°C;T5@50°C;T6@40°C
FOR INSTALLATION AND MAINTENANCE SEE CONTROL
DRAWING SG4-3770-01
0891
TYPE: Pt100
RANGE: 0-100°C
SEM310X HART
SER No. 000000 - 0001
R
www.status.co.uk