User instruction for SEM210X electrical apparatus for use in a hazardous area.
Important: Read and understand this document before any installation.
ATEX
& IECEx
Instructions
For safe installation of the SEM210X in hazardous areas the following instructions must be observed. The transmitter must be installed by
competent personnel, who are familiar with national and international laws, directives and standards that apply to their region. For
installation in European Economic Area (EEA) member countries users must follow requirements for electrical equipment for use in
potentially explosive atmospheres, e.g. EN60079-14 & EN60079-17. This instruction sheet describes installation, which conforms with BS
EN60079-14 & BS EN60079-17. Important - Particular attention must be paid to the section titled "Special conditions for safe use", failure
to comply to this requirement will result in an unsafe system.
The SEM210X has been issued with a EU-type examination certificate, confirming compliance with European ATEX directive 2014/34/EU
for the following specification :-
Manufacturer
Status Instruments Ltd
Type Number
SEM210X
Zones
Product Information
Certificate Ref
EMT16ATEX0005X
Classification
The following Information is printed on the
product label
Working Parameters
Additional Information
EMC
BS EN 61326-1
(Sensor wires maximum length 3 metres to comply.)
Enclosure
Colour Blue
SER No. 000000 - 0001
www.status.co.uk
Made in UK
0891
II 1 GD
IECEx TRC 10.0008X
Ex ia IIC T4 Ga
Ex iaD 20 T135 °C Da
Tamb = -40 °C to 85 °C
Terminals
+ / -
Ui
=
30 V
Ii
=
100 mA
Pi
=
750 mW
Ci
=
0
Li
=
0
Uo =
-
Io
=
-
Po
=
-
D2578-01-02 SEM210X User Guide
Page 1 of 4
Area Classification
Gases
Dusts
Zone Criteria for Application Atmosphere
Zone 0
Zone 20
Present continuously or for long periods
(> 1000 hours per annum)
Zone 1
Zone 21
Likely to occur in normal operation occasionally
(> 10 to < 1000 hours per annum)
Zone 2
Zone 22
Unlikely to occur in normal operation
(< 10 hours per annum)
“Model”
TRAC ????
SEM210X
2016-11
Example of Type and Range shown below