background image

To fit or release module

Insert screw driver into

slot and lever latch

away from body

MECHANICAL INSTALLATION

Enclosure

Style

DIN Rail Mount

Material       

Blend PC/ABS self extinguishing

Terminals

Screw terminal

Cable

2.5 mm Max

Colour

Gray

Ø 3  mm

MOUNTING

Screw driver

EN60715 DIN RAIL

1

2

Ambient Range

+ 70 °C Max

- 20 °C Min

Ø 3mm

Screw Driver

Shielded Cable

Twisted Pair Cable

TC Compensation Cable

Screened 

TURN 

OFF 

SUPPLY 

BEFORE   

WORKING  ON  ANY  ELECTRICAL 
CONNECTION

INPUT CONNECTION
For cable length  < 3 Meters no shielded 
cable or twist pair required.
Thermocouple inputs must use correct 
compensation cable.
Pt100 inputs all three wires must be equal 
length (resistance).
Max input cable length 30 meters.

Temperature

Process

Current  

Externally 

Powered

Voltage

TRIP 1(A)

TRIP 2(B)

Current 
Internal  

Powered

ANALOG OUTPUT  CONNECTION
For cable length  < 3 meters no shielded cable 
or twisted pair required.
Use twisted pair or shielded cable for current 
output < (30 to 1000)  meters.
Voltage output use shielded cables  (3 to 30)
 meters, cable lenghts > 30 meters not advised.

TRIP OUTPUT 
CONNECTION
Trip outputs are isolated 
from each other.
Max switching current 1 A 
@ 240 V ac, 1 A @ 30 V dc

SUPPLY  CONNECTION
Supply input is not polarity 
sensitive.
Max supply 240 V ac or 
240 V dc

ELECTRICAL  INSTALLATION

+

-

T/C

4

2

PT100

5

2

3

Slide Wire

V

+

-

V /mV

4

mA

+

-

mA Sense

T
x

+

-

Transmitter

1

3

3

4

2

6

4

2

Load

7

8

V s

+

-

Load

8

9

Vout

10

7

+

-

8

16

17

18

a

b

c

14

13

15

a

b

c

11

12

a.c.

d.c.

+

-

IMPORTANT -  CE  &  SAFETY REQUIREMENTS 

This product is suitable for enviroment Installation category II  pollution degree.
The product is classed as "PERMANENTLY CONNECTED EQUIPMENT".
Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
DC supply must be derived from a local supply and not a distribution system.
Max relay contact rating 240 V AC @ 1 a (30 V DC @ 1A). Any circuit connected to a contact must be fused with a 2 A (T) fuse.
To maintain CE EMC requirements , input and supply wires  must be less than 30 meters.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.

ABSOLUTE MAXIMUM  CONDITIONS:-

Supply Voltage

± 240 V dc  ± 240 V ac (Protected for over voltage )

Input Voltage

± 24 V  between any terminals

Input Current

± 50 mA between terminals 

Output

30 V dc 

Trips

240V ac @ 1A 30V dc @ 1A  non inductive 

Ambient

Temperature 

(-4 to 158) °F  Humidity (10 to 95) % RH (Non condensing)

PRODUCT SPECIFICATION

Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.

RECEIVE AND UNPACKING

Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier 
immediately.

CONFIGURATION

IMPORTANT During configuration the device takes its power from the USB port, therefore no power connection is required.  The device can be configured while powered 

but the computer used must be isolated from the mains supply earth to avoid ground loop effects.

Device

M-CONFIG  or USB_LINK software 

(usb_link V2.0 or greater)

USB CABLE

Disk or download @ 

www.statInst.com

COMPUTER

The following parameter can be configured by simply entering as prompted by the software package. 

· Input type / input sensor / units(temperature inputs) / sample rate 
· Scale  input to process variable (process inputs only) 
· Analog Output / Set Type voltage or current / scale  output signal range / scale output to process
  Set adjustable damping for both rising and falling output. Set correction for voltage output load.
· Trip Outputs / Set action / Set setpoints / Set deadband / Set adjustable delay on and delay off 
· Set burnout direction on sensor failure or input overrange.
· Set the function of the front panel user buttons to off, trim or configure.
. TAG number

Factory default:

Input type

= P

Sample rate  = 1000 mS
Units

= °C

Output 

= (4 to 20) mA damping 0

 

High Range = 100

 

Low Range = 0
Burnout

= UPSCALE

User Trim

= off

Trips

= off, delays 0

Damping        = 0

           Status Instruments Inc,    PO Box 548,    456 Park Avenue,    Scotch Plains, NJ  07076

Web Page:  www.statinst.com    Tel : (800) 700-3272    Fax: (800) 700-5468   email : [email protected]

SEM1700 USER GUIDE

Temperature/Process Conditioner  with 
Universal input, outputs supply plus 
manual config/trim.

Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.

Important - Please read this document before any installing.

INPUT

2

3

4

5

External Powered

(4-20) mA Output

SEM1700

8

9

1

7

Internal  Powered

current Output

14

13

15

16

17

18

a

a

b

b

c

c

TRIP 1 (A)

TRIP 2 (B)

12

11

ANALOGUE OUTPUT

USB

6

Slide Wire

PT100

V

+

+

-

-

T/C

V /mV

4

4

2

Temperature

5

2

3

Process

mA

+

-

mA Sense

T
x

+

-

Transmitter

1

3

3

4

2

6

4

2

V s

+

-

Load

7

8

Load

8

9

TRIP OUTPUT

10

Vout

10

7

+

-

Voltage

OUTPUT

8

SUPPLY (20 to 240) V AC or DC

All Dimensions in mm