background image

D2534-01-04 

 

SEM1600B 

USER INSTRUCTIONS 

 

Important - Please read this document before installing. 

Every effort has been taken to ensure the accuracy of this document; however, we do 

not accept responsibility for damage, injury, loss or expense resulting from errors and 

omissions, and we reserve the right of amendment without notice. 

IMPORTANT – CE, UKCA & SAFETY REQUIREMENTS 

 

Product must be DIN rail mounted, inside a suitable enclosure providing environmental 

protection to IP65 or greater. 

To maintain CE UKCA requirements, input and supply wires must be less than 30 

metres. 

The product contains no serviceable parts, or internal adjustments. No attempt must be 

made to repair this product. Faulty units must be returned to supplier for repair. 

Before attempting any electrical connection work, please ensure all supplies are 

switched off. 

 

ABSOLUTE MAXIMUM CONDITIONS (To exceed may cause damage 

to the unit). 

Supply voltage (SELV) 

± 50 Vdc Protected for over-voltage 

and reverse connection 

Current with over-voltage 

± 200 mA 

Input voltage 

± 10 VDC between any terminals 

Input current 

± 100 mA between any terminals 

Environmental protection 

IP65 or greater required 

Ambient 

Temperature (-30 to 75) °C 

RH (10 to 95)% non-condensing 

 

Important – Read this 

document before installing.

 

 

-------------------------------------------------------------------------------------------------------------- 

1~DESCRIPTION

The

 SEM1600B is a powered bridge amplifier for use with strain 

gauges or load cell signals. The product has a built-in capability to 

scale the input signal to a process value while the output stage offers 

either voltage, bipolar voltage or active/passive current retransmission 

signals. The device uses ratio metric measurement to obtain high  

stability.  

The

 product comes with an AC/DC power supply that will operate in 

the range (10 to 48) VDC and (10 to 32) VAC making the device ideal 

for battery operation. An additional volt-free contact input is available 

for tare setting using a remote switch. The high precision input stage 

of the device allows for a bridge excitation voltage of 5 VDC to be 

used, as opposed to the traditional 10 VDC. This reduces the power 

requirement for the bridge supply and up to four bridges (cells) may 
be connected to the input

.

 

To

 configure: connect a standard USB cable between the SEM1600B 

and a PC. The free configuration software will guide you through any 

changes you wish to make. The SEM1600B does not need to be 

wired to a power supply for configuration. 

 

2~RECEIVING AND UNPACKING

Please 

inspect the packaging and instrument thoroughly for any signs of transit 

damage. If the instrument has been damaged, please notify your supplier immediately.  

 

3~SPECIFICATION.

 

Refer

 to the datasheet for full specification. Download at 

www.status.co.uk

  

Factory 

defaults 

Calibration factor 2 mV/V, Balance 0.0 

Sample rate 10 per s, Filter Off 

Scale 2 points 

Tare Setpoint 0, Tare Offset 0 

Process Output 0 to 100 = (4 to 20) mA 

Button locks Off 

4~INSTALLATION AND WIRING. 

Important safety requirements

 

This

 equipment is suitable for Environment Installation BS EN61010-1 

Pollution Degree 2; Installation CAT II; CLASS I and is classed as 

"PERMANENTLY CONNECTED EQUIPMENT". The equipment is 

intended for industrial and commercial application only and is not 

suitable for domestic or medical use. 

The

 equipment must be mounted inside an enclosure that provides 

protection >= IP65. In NORMAL USE, the equipment will only be 

accessed for maintenance by qualified personnel.  

Please 

ensure the equipment is mounted vertically with terminals (10, 

11 and 12) at the bottom. This will provide maximum ventilation.  

This

 equipment may generate heat. Ensure the enclosure size is 

adequate to dissipate heat. Be sure to consider any other equipment 

inside the enclosure. 

The

 equipment surfaces may be cleaned with a damp cloth. Use a 

mild detergent/water. Ensure the supply is off before cleaning and, on 

completion of cleaning, the equipment is completely dry before the 

supply is turned back ON. 

This

 equipment must be installed by a qualified person. All electrical 

wiring must be carried out in accordance with the appropriate 

regulations for the place of installation. 

 

4.1~MECHANICAL. 

Dimensions in mm  

56.4 mm

17.5 mm

1

2

11 12

10

9

8

7

4

5

6

1

2

3

90mm

ADJUST

STATE

 

The

 equipment must be mounted on a DIN rail style DIN EN50022 

inside a plastic or metal enclosure with a protection level >= IP65. All 

wiring must be secured. Maximum cable sizes 2.5 mm². Connection is 

via screw clamp terminals. 

 

4.2~ELECTRICAL/CONNECTIONS 

 

For

 wiring connections refer to the side label on the SEM1600B and 

this document. 

Supply 

(10 to 48) Vdc, (10 to 32) Vac 

To 

maintain CE EMC requirements, input and supply wires must be 

less than 30 metres. 

Input

 cable lengths > 3 m it is recommended to use screened or 

twisted pair. 

Maximum

 mA output cable run = 1000 metres. The output loop 

should be grounded at a single point. 

Before 

installation, care must be taken to ensure enough voltage is 

available in any loop to drive the total loop load.  

 

 

 

 

 

 

 