background image

The SEM1401 is a single trip amplifier.

Type

Two wire (4 to 20) mA, 50 mA max.

Protection

Reverse connection protected

Loop Drop

5 V max.

Alarm

HIGH or LOW level, switch selected, side entry

Contact

Single relay changeover with N/O / N/C contacts available

Rating

Resistive Load 2 A @ 250 VAC/125 VDC max. Power 150 W (Inductive Loads)

Indication

Alarm LED on module front face

Set point

(0 to 100) % multi turn potentiometer, access on module front face 
(Repeatability ± 0.2 %)

Hysteresis

(0.1 to 5) % Single turn trim pot on module front face

Delay 

0.5 second fixed delay

Failure Mode

On loss of signal:- HIGH level No alarm condition; LOW level alarm 
condition (i.e. Alarm operates as if signal has fallen to -25 % or 0 mA)

Minimum Current

3.5 mA

Isolation

3000 VAC rms between contacts and input 1000 VAC rms between contacts

Ambient

(0 to 50) ºC; (10 to 95) % RH non condensing

Connection

Captive clamp screws

Cable Size

4 mm² solid/2.5 mm² stranded

Case Material

Grey Polyamide

Case Flammability

To UL94-V0 VDE 0304 PT3 level 111A

Dimensions

(60 x 60 x 21) mm (67.5 mm above rail)

Mounting 

Snap on “Top Hat” (DIN EN 50022-35)

Max Vibration

12 G (10 to 55) Hz at double amplitude 2 mm

Shock Res.

12 G

Compliant With

EN50081-1, EN50082-1

Weight

100 grams

Page 1

 

 

WARNING! 

Hazardous voltages may be present on the terminals - the equipment must 
be installed by suitability qualified personnel and mounted in an enclosure 
providing protection to at least IP20.

 

WARNING!

If not installed and used in accordance with these instructions, protection 
against hazards may be impaired.

 

IMPORTANT NOTE

it may be preferred to set the user adjustment on the bench prior to 
installation. Please read Section 3.0 before installation.

This trip must be housed within a suitable enclosure that will provide protection from the external 
environment, to ensure that the stated temperature and humidity operating ranges are maintained. As
SEM1401 contains a high quality relay, care must be taken to ensure the trip is not subjected to strong
shock or vibration, as this may result in momentary opening of the relay contacts. The SEM1401 must not
be located near a strong magnetic field, such as a transformer, solenoid or electric motor.

The SEM1401 case is designed to snap fit onto a standard “Top Hat” DIN rail. To remove from DIN rail, apply
pressure at the bottom face of the back upwards towards the rail to release the spring clip and tip away
from the top.  The trip may be mounted in any orientation and stacked side by side along the rail.

Connections to the trip are made via screw terminals, with wire protector plates provided inside each 
terminal. To maintain CE compliance twisted pair (screened) cables are recommended for signal connections.
It is also good practice to ensure that all (4 to 20) mA loops are grounded at a single point. Before 
installation ensure the (4 to 20) mA loop has enough voltage available to drive the trip. Refer to the above
specification for the loop voltage drop. The change over contacts provided by the SEM1401 are capable of
switching 250 VAC 125 VDC @ 2 A resistive load, 150 W inductive load. Internal Varistors are connected
across the contacts to  protect against over voltage. It is advised that a external R/C snubber  network is
used when switching inductive AC loads (see Figure 1). When switching DC inductive loads, a diode 
connected in parallel with the inductor must be used to protect the contacts from the energy stored in
the inductor (See Figure 2).

Installation overvoltage Category 2 (as per BS EN61010-1)

If this equipment is to be used in environments with overvoltage Category 3, transient suppressors 
should be installed on wiring carrying greater than 50 VAC or 75 VDC.

Any power supply to the equipment greater than 50 VAC or 75 VDC must be protected by a suitable 
fuse and a switch or circuit breaker which should be near the equipment.

The equipment contains no user serviceable parts.

Page 2

1.0 DESCRIPTION

3.0 INSTALLATION

2.0 SPECIFICATIONS

2.1 INPUT

2.2 OUTPUT

2.3 GENERAL SPECIFICATION

3.1 MECHANICAL

3.2 ELECTRICAL

Содержание SEM1401

Страница 1: ... ALARM TRIP SET UP 3 4 5 0 OPERATION 4 6 0 MECHANICAL 5 Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 214 2410 01 Issue Web 1401 SEM1401 INDEX Loop Powered Trip Amplifier ...

Страница 2: ...y relay care must be taken to ensure the trip is not subjected to strong shock or vibration as this may result in momentary opening of the relay contacts The SEM1401 must not be located near a strong magnetic field such as a transformer solenoid or electric motor The SEM1401 case is designed to snap fit onto a standard Top Hat DIN rail To remove from DIN rail apply pressure at the bottom face of t...

Страница 3: ...t the task is greatly simplified by replacing the process signal with a adjustable 4 to 20 mA current source to simulate the 4 to 20 mA process signal The set up process is as follows 1 First decide on the type of trip required High for alarm ON state above set point or Low for alarm ON state below set point Set the High Low alarm selection switch on the side of the enclosure to the desired settin...

Страница 4: ...er information on all products Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk ALSO AVAILABLE Hi Lo Switch Select SEM1401 HYS TRIP IN C N C N O SERIAL NO OUT RELAY 2 A 250 VAC IN 2 WIRE 4 to 20 mA www status co uk OUT LO HI Figure 3 60 0 mm 21 0 mm 60 0 mm 6 0 MECHANICAL DETAIL Page 5 P...

Отзывы: