The options are:
noninv
( energise relay on alarm, de-energise normally )
i
Nv
( energise normally, de-energise relay on alarm )
This function is tied in with the fail safe requirements of the relay and its electrical
configuration. The following summarises all options.
Default setting:
noninv
4.2.3.1.7 dElAy ( Delay before activation of alarm)
This option allows a delay time to be programmed ( in seconds ) which must elapse
between an alarm being detected and then indicated ( and relay state changed ).
The options are:
oFF
( No delay time )
1 SEC
( 1 second delay )
2 SEC
( 2 second delay )
5 SEC
( 5 second delay )
10 SEC
( 10 second delay )
15 SEC
( 15 second delay )
20 SEC
( 20 second delay )
If the alarm condition is removed during the delay period and then re-applied, the
delay time starts again from the time the alarm condition re-occurs.
Default setting:
OFF
OUTPUT MENU
PROGRAMMING
Page 54