Display Flashes 

“05”

 when button is pressed:

Display Flashes 

“15”

 when button is pressed:

Display Flashes 

“25”

 when button is pressed:

ECO SWITCH OPEN. See Figure 21.

ECO LED Flashing:

ECO SWITCH OPEN, ECO LED Flashing

FIGURE 21.

CONTROL BAD. See Figure 22.

All LEDs Flashing:

Possible Cause

Remedy

1. This indicates the control has

1. Press button on the

failed on of its internal

display board to reset

diagnostic  self-tests.

control.  If this error
occurs repeatedly,
replace control.

CONTROL BAD, All LEDs Flashing

FIGURE 22.

COMBUSTION AIR BLOCKAGE. See Figure 23.

Pressure Switch LED Flashing:

COMBUSTION AIR BLOCKAGE, Pressure Switch LED Flashing

 FIGURE 23.

Possible Cause

Remedy

1.  Temperature Probe wiring

1. Repair Wiring

open

2. Defective probe

2. Replace probe

Possible Cause

Remedy

1.  No water in tank and tank

1. The symptom does not

in freezing conditions

reflect a control problem

2. Water in tank above freezing

2. Temperature probe out of

tolerance, replace temp.
probe

Possible Cause

Remedy

1.  Water in tank is low, probe

1. Fill tank

immersed in steam

2. Probe wiring shorted

2. Repair wiring

3. Defective probe

3. Replace probe

Possible Cause

Remedy

1.  Temp. Probe unplugged

1. Check connectors

2. Temp. probe wiring damaged

2. Repair wiring

3. Water in tank too hot

3. Normal condition when

water t e m p e r a t u r e
exceeds safety limit.
Allow water to cool or
admit water into tank and
manually reset the control.
Determine cause for
overtemp condition.

Possible Cause

Remedy

1. Combustion air blocked

1. Check exhaust piping and

flue for obstructions

2. Blower not operating:

2. a. Repair wiring

a. Check blower wiring

b. Replace blower motor

b. Check blower motor

3. Defective air switch

3. Replace air switch

4. Pressure switch jumped out

4. This controller must  sense

an open contact on the
blower proving airflow
switch before the blower
comes on. Check to see if
blower proving airflow
switch is still connected to
the unit.

Содержание ULTRA FORCE SUF-130-300

Страница 1: ...D USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing prope...

Страница 2: ...n Code and CSA C22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 NFPA documents are also availabl...

Страница 3: ...18 Gas Value LEDs Flashing 18 Error Codes 19 Fault Conditions 19 No Incoming Line Voltage 19 No Low Voltage 19 Temperature Probe Fault 19 20 E C O Switch Open 20 Control Bad 20 Combustion Air Blockag...

Страница 4: ...4 AT A GLANCE QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Страница 5: ...ider using lower temperature settings to reduce scald hazards Temperature Time to Produce 2nd 3rd Setting Degree Burns on Adult Skin 180 F 82 C Nearly instantaneous 170 F 77 C Nearly instantaneous 160...

Страница 6: ...a storage tank used in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National E...

Страница 7: ...If the unconfined space is within a building of tight construction buildings using the following construction weather stripping heavy insulation caulking vapor barrier etc air for combustion and vent...

Страница 8: ...RECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECO...

Страница 9: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Страница 10: ...tional Fuel Gas Code and local Codes IMPORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMI...

Страница 11: ...e about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent terminal 7...

Страница 12: ...the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to use a minimum of 0 equivalent feet of 4 inch PVC pipe IMPORTANT When multiple uni...

Страница 13: ...a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner the pressure switch will allow the electrical contacts to close The pressure sw...

Страница 14: ...PPLIERS REFER TO THE NATIONAL FUEL GAS CODE OR THE NATURALGAS AND PROPANE INSTALLATION CODE CSA B149 1 FIGURE 14 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only N...

Страница 15: ...ystems ANSI Z21 22 CSA 4 4 Your local code authority may have other specific relief valve requirements WARNING THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEA...

Страница 16: ...GH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY The controller is wired to the heater a...

Страница 17: ...17 FIGURE 16...

Страница 18: ...ng the proper state of the air switches and ECO limit device 4 If all checks are successfully passed the combustion blower is energized for the pre purge cycle 5 When the pre purge cycle is complete p...

Страница 19: ...mplemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed State...

Страница 20: ...t a control problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiri...

Страница 21: ...ON OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYAND ELECTRICAL WORKARE REQUIRED Before attemp...

Страница 22: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Страница 23: ...CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 F...

Страница 24: ...the hardness lime For this reason it is recommended that a regular schedule for deliming be maintained The depth of lime buildup should be measured periodically Heaters will have about 3 7 6cm of lim...

Страница 25: ...e freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended size as necessary Inspection of the valve should be performed at least ever...

Страница 26: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Страница 28: ...CIFICATIONS PAGE 30 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 29: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 30: ...E 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE...

Страница 31: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Страница 32: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WATE...

Страница 33: ...nate the problem replace the pressure switches 5 Check to see if there is resistance across the igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replace...

Страница 34: ...ed immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 r...

Страница 35: ...method d This warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by att...

Страница 36: ...36 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Отзывы: