is
Release R.1.0 Uk
58
Warning
Maintenance may only by carried out by a service and maintenance engineer.
8.3
Fault table 'no hot water'
If the appliance is not supplying any hot water, this can have a variety of causes.
Then consult the table
Table 8.2 No hot water
Page 1 of 2
Characteristic
Cause
Measure
Observation
Green LED OFF
and
Red LED OFF
No supply voltage
1. Check whether the main switch is ON.
2. Check the voltage across the main switch.
3. Check the voltage across the electrical connecting block.
4. Check voltage across the burner controller.
5. Check fuse in the burner controller.
The measured voltage must be 230V AC +15% -10%.
See appendix
. If the fault cannot be
resolved, then contact your installer.
Green LED ON
and
Red LED OFF.
Blockage in the flue
gas outlet (the flue gas
cut-out has switched)
1. Detect blockage.
2. Remove blockage.
3. Reset flue gas cut-out. See paragraph
When there is a heat demand, the appliance comes into operation.
Содержание SCE 65-400
Страница 2: ...your installer ...
Страница 4: ...4 SCE Instruction Manual ...
Страница 8: ...8 Instruction Manual SCE gis ...
Страница 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Страница 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Страница 20: ...Installation 20 Instruction Manual SCE 3 is Figure 3 1 Top and front of the appliance IMD 0145 ...
Страница 42: ...Installation 42 Instruction Manual SCE 3 is ...
Страница 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Страница 64: ...Maintenance 64 Instruction Manual SCE 9 s ...
Страница 67: ...Release R 1 0 Uk 67 A Appendices A 1 Introduction This appendix contains The Electrical diagram SCE is ...
Страница 70: ...Appendices 70 Instruction Manual SCE A is ...