Installation
22
Instruction Manual SCE
3
is
3.3.3
Maximum floor load
Owing to the weight of the appliance, the maximum floor load should be taken
into account, see
3.3.4
Water composition
The appliance is intended to heat drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
indicates the requirements in respect of this.
n
Remark
If there is any deviation from the specifications stipulated in
, then
the tank protection cannot be guaranteed.
See also chapter
3.4
Technical
specifications
The appliance is supplied without accessories. Check the measurements and
other specifications for the accessories to be used based on
and
tables
.
Table 3.2
Weight specifications with regard to maximum floor load
Weight of the appliance filled with water
SCE 80-115 SCE 80-140 SCE 80-180 SCE 95-199 SCE 95-260 SCE 70-360 SCE 65-400 SCE 65-500
523 kg
523 kg
525 kg
594 kg
597 kg
540 kg
531 kg
582
Table 3.3
Water specifications
Water composition
Hardness
(alkaline-earth ions)
> 1.00 mmol/l:
•
German hardness > 5.6° dH
•
French hardness > 10.0° fH
•
British hardness > 7.0° eH
Conductivity
> 125
µ
S/cm
Acidity (pH value)
7,0 < pH value < 9.5
Table 3.4
Dimensions SCE
Dimension Description
SCE
80-115
SCE
80-140
SCE
80-180
SCE
95-199
SCE
95-260
SCE
70-360
SCE
65-400
SCE
65-500
A. Height including draught diverter (mm)
1910
1910
1890
2155
2155
1950
2145
2145
B. Height excluding draught diverter (mm)
1690
1690
1690
1900
1900
1735
1810
1810
D. Diameter of the appliance (mm)
710
710
710
710
710
710
710
710
F. Width including control column (mm)
800
800
800
800
800
800
800
800
G. Flue gas outlet diameter (mm)
130
130
150
180
180
200
250
250
K. Height of the gas connection (mm)
145
145
145
145
145
145
145
145
M. Height of the cold water supply (mm)
505
505
505
505
505
515
590
590
N. Height of the hot water outlet (mm)
1545
1545
1545
1750
1750
1580
1655
1655
Содержание SCE 65-400
Страница 2: ...your installer ...
Страница 4: ...4 SCE Instruction Manual ...
Страница 8: ...8 Instruction Manual SCE gis ...
Страница 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Страница 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Страница 20: ...Installation 20 Instruction Manual SCE 3 is Figure 3 1 Top and front of the appliance IMD 0145 ...
Страница 42: ...Installation 42 Instruction Manual SCE 3 is ...
Страница 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Страница 64: ...Maintenance 64 Instruction Manual SCE 9 s ...
Страница 67: ...Release R 1 0 Uk 67 A Appendices A 1 Introduction This appendix contains The Electrical diagram SCE is ...
Страница 70: ...Appendices 70 Instruction Manual SCE A is ...