13

minimum inlet gas pressure shown on the rating plate is that 
which will permit 

fi

 ring at rated input.

All gas piping must comply with local codes and ordinances or 
with the National Fuel Gas Code ANSI Z223.1/NFPA 54 which-
ever applies. Copper and brass tubing and 

fi

 ttings (except tin 

lined copper tubing) shall not be used.

If the gas control valve is subjected to pressures exceeding 1/2 
psi (3.5 kPa), the damage to the gas control valve could result in 

fi

 re or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, 
also turn “off” the gas at each appliance.  Leave all gas appli-
ances shut “off” until the water heater installation is complete.

A gas line of suf

fi

 cient size must be run to the water heater.  

Consult the current edition of National Fuel Gas Code ANSI 
Z223.1/NFPA 54 and your gas supplier concerning pipe 
size.

There must be:
•  A readily accessible manual shut off valve in the gas supply 

line serving the water heater, and

•  A drip leg (sediment trap) ahead of the gas control valve to 

help prevent dirt and foreign materials from entering the gas 
control valve.

• A 

fl

 exible gas connector or a ground joint union between the 

shut off valve and control valve to permit servicing of the 
unit.

Be sure to check all the gas piping for leaks before lighting the 
water heater.  Use a soapy water solution, not a match or open 

fl

 ame.  Rinse off soapy solution and wipe dry.

When installed at elevations above 7,700 feet (2,347 meters), input 
rating should be reduced at the rate of 4 percent for each 1,000 feet 
(305 meters) above sea level which requires replacement of the 
burner ori

fi

 ce in accordance with National Fuel Gas Code ANSI 

Z223.1/NFPA 54.  Contact your local gas supplier for further 
information.

Failure to replace the standard ori

fi

 ce with a high altitude ori

fi

 ce 

when installed could result in improper and inef

fi

 cient operation 

of the appliance, producing carbon monoxide gas in excess of 
safe limits, which could result in serious injury or death. Contact 
your gas supplier for any speci

fi

 c changes which may be re-

quired in your area. 

Use pipe joint compound or te

fl

 on tape marked as being resis-

tant to the action of petroleum [Propane (L.P.)] gases. 

The appliance and its gas connection must be leak tested before 
placing the appliance in operation.

The appliance and its individual Shut-off valve shall be disconnected 
from the gas supply piping system during any pressure testing of 
that system at test pressures in excess of 1/2 pound per square inch 
(3.5 kPa).  It shall be isolated from the gas supply piping system 
by closing its individual manual Shut-off valve during any pres-
sure testing of the gas supply piping system at test pressures 
equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting the gas piping to the gas control valve of the water 
heater can be accomplished by either of the two methods shown 
in Figures 8 and 9.

FIGURE 8 GAS PIPING WITH

FLEXIBLE CONNECTOR.

FIGURE 9 GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

Содержание 186589-001

Страница 1: ...N ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER GAMA certification applies to all residential gas water heat ers with capacities of 20 to 100 gallons with input rating of 75 000 BTU Hr or less A Brand of State Industries Inc Ashland City TN 37015 www statewaterheaters com ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF...

Страница 2: ...NT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features and use of fl...

Страница 3: ...3 GENERAL SAFETY ...

Страница 4: ...Mechanical Engineers GAMA Gas Appliance Manufacturer s Association UL Underwriters Laboratories Inc This gas fired water heater is design certified by Underwriters Laboratories Inc under American National Standard CSA Stan dard for Gas Water Heaters ANSI Z21 10 1 CSA 4 1 current edition PREPARING FOR THE INSTALLATION 1 Read the General Safety section page 3 of this manual first and then the entire...

Страница 5: ...ntally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and si...

Страница 6: ...LOCAL CODES THERMAL EXPANSION TANK INSTALLTHERMALEXPANSION TANK IF WATER HEATER IS INSTALLED IN A CLOSED SYSTEM GAS CONTROL TYPICAL INSTALLATION FLUE BAFFLE GAS SUPPLY LINE MAIN MANUAL GAS SHUTOFF VALVE GROUND JOINT UNION DIRT LEG ANODE HOT WATER OUTLET PIPE UNION INLET DIP TUBE TEMPERATURE AND PRESSURE RELIEF VALVE DISCHARGE PIPE DO NOT CAP OR PLUG WATER TEMPERATURE ADJUSTING DIAL DRAIN VALVE DRA...

Страница 7: ...the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs a means such as a Mixing Valve should be used at the hot water taps used by these people or at the water heater Mix ing valves are available at plumbing supply or hardware stores Consult a Qualified Installer or Service Agency Follow mixing valve...

Страница 8: ...Water heater life depends upon water quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped dr...

Страница 9: ...ATION FOR APPLIANCES LOCATED IN CONFINED SPACES FIGURE 3 Confined Space is a space whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 cm per kW of the aggregate input rating of all appliances installed in that space VENT TERMINATION Before installing water heater determine placement of vent ter mination Make certain to observe vent location limitation see Figures 3 4 12 Minimum cle...

Страница 10: ... heating systems or component s used with a non potable water heating appli ance All piping components connected to this unit for space heating applications shall be suitable for use with potable water Toxic chemicals such as those used for boiler treatment shall not be introduced into this system When the system requires water for space heating at tem peratures higher than required for domestic w...

Страница 11: ... TEMPERATURE PRESSURE RELIEF VALVE This heater is provided with a properly certified combination temperature pressure relief valve by the manufacturer The valve is certified by a nationally recognized testing labora tory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 an...

Страница 12: ...and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and re place the temperature pressure relief valve with a new one WATER POTABLE HEATING AND SPACE HEATING 1 All piping components connected to this unit for space heating applications shall be suitable for use with potable water 2 Toxic chemicals such as those used for boiler ...

Страница 13: ...y solution and wipe dry Wheninstalledatelevationsabove7 700feet 2 347meters input rating should be reduced at the rate of 4 percent for each 1 000 feet 305 meters above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code ANSI Z223 1 NFPA 54 Contact your local gas supplier for further information Failure to replace the standard orifice with a high al...

Страница 14: ... must be filled with water Water must flow from the hot water faucet before turning ON gas to the water heater To fill the water heater with water 1 Close the water heater drain valve by turning the handle clockwise The drain valve is on the lower front of the water heater 2 Open the cold water supply valve to the water heater NOTE The cold water supply valve must be left open when the water heate...

Страница 15: ...bove if within 10 ft 3 m horizontally to a mechanical air supply inlet Minimum 12 in 30 cm from sides above or below a permanently closed window or door Minimum 7 ft 2 3 m above public sidewalk or paved driveway see footnote 2 Minimum 9 in 23 cm for appliances with 10 000 btuh 3 Kw to 50 000 btuh 15 Kw inputs and 12 in 30 cm for appliances greater than 50 000 btuh 15 Kw to a non mechanical air sup...

Страница 16: ... gal Hi Input and 75 gal models as measured from the hole center to bottom of water heater The maximum height recommended is 80 in 2 03m or in compliance with Figure 16 Where the wall is combustible and the wall thickness is over 14 in 356mm 1 in 25mm clearance to combustible materials around the vent terminal is needed The first 14 in 356mm is zero clearance 7 in 178mm DIAMETER BOTTOM OF HEATER S...

Страница 17: ...unction of the outer corrugated tube and the trim plate inside with suitable sealant SEALANT TRIM PLATE INSIDE TRIM PLATE OUTSIDE FIGURE 19 UNCOMPRESSING THE CORRUGATED TUBING 1 Pull the inner corrugated tube towards the water heater and leave some length over the water heater s center for bending 2 Pull the outer corrugated tube toward the water heater and leave it 1 in 25mm shorter than the inne...

Страница 18: ... corrugated tube TOP VIEW 90 MAXIMUM BEND FIGURE 26 CONDITION 2 Where floor joists impede venting a rise or drop to complete the vent termination is possible All installations require 1 in 25mm clearance to combustibles Note A The maximum horizontal vent length of 80 in 2 03m minus wall thickness should be considered when installing an offset vent arrangement B Do not combine condition 1 Figure 26...

Страница 19: ...y call your service technician or gas supplier If the pilot will not stay lit after several tries turn the gas control knob clockwise to OFF and call your service technician or gas supplier SEE FIGURE A 11 Once the pilot flame is established replace the outer burner door 12 At arm s length away turn gas control knob counterclockwise to ON SEE FIGURE C 13 Set thermostat to desired setting DANGER Ho...

Страница 20: ... by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30 F 17 C If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing point of use temperature by mixing cold and hot water are available see Figures 2 7 Also available are inexpensive devices that attach to faucets to...

Страница 21: ...e effects of water hammer among others have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heated it expands thermal expansion and closed systems do not allow for the exp...

Страница 22: ...ossibility of injury under these conditions we recommend the hot water faucet located farthest away be opened for several minutes before any electri cal appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened T...

Страница 23: ...ter heater will create dangerous conditions which can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAM AGE Contact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made of the main burner and the pilot assembly for proper flame characteris tics This can be done by remo...

Страница 24: ...water to run until it flows clean This will help prevent sediment build up in the tank It is normal for lime and scale deposits to form within the tank Such deposits will not be removed by periodic draining It is necessary to chemically delime the affected parts in water areas where such deposits are encountered Contact your dealer or plumber for deliming information CATHODIC PROTECTION ANODE The ...

Страница 25: ...ter heater 2 Follow Draining instructions 3 Turning counterclockwise remove the hex cap below the screw handle 4 Remove the washer and put the new one in place 5 Screw the handle and cap assembly back into the drain valve and retighten using a wrench DO NOT OVER TIGHT EN 6 Follow instructions in the Filling The Water Heater section 7 Check for leaks 8 Follow the lighting instructions in the Lighti...

Страница 26: ...g may be leaking anode is located under the Blower Assembly D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pres sure in your area E The temperature pressure relief valve may be leaking at the tank fitting F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Comb...

Страница 27: ...h gas utility company 3 Notify utility install dirt trap in gas line 4 Clean locate source and correct 5 Finger tighten then 1 4 turn with wrench 6 Replace thermocouple 7 Locate source and correct 8 Replace gas control thermostat 9 Call a qualified service technician 10 Replace igniter or pilot assembly 11 Replace water heater eliminate flammable vapors source Call a qualified service tech nician ...

Страница 28: ...d 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle burner 2 Clean locate source and correct 3 Provide fresh air ventilation SMOKING AND CARBON FORMATION SOOTING 1 Insufficient secondary air 2 Low gas pressure 3 Flue clogged 4 Defective gas control thermostat 5 Heater installed in a confined area 6 Burner flame yellow lazy 1 Provide ventilation ...

Страница 29: ...29 NOTES ...

Страница 30: ... the working pres sure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale deposits used in a non corrosive and non contaminated atmo sphere used with factory approved anode s installed in its original installation location in the United States its territories or possessions and Canada sized in accordance with prop...

Страница 31: ...tz Parkway Ashland City TN 37015 phone 1 800 821 2017 The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor Dealer replacements are made subject to in warranty valida tion by warrantor PROOF OF PURCHASE AND PROOF OF INSTALLATION DATE ARE REQUIRED TO SUPPORT WARRANTY CLAIM FROM ORIGINAL OWNER THIS FOR...

Страница 32: ...32 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 PHONE 800 821 2017 FAX 800 644 9306 www statewaterheaters com ...

Отзывы: