Digimon TFT rev.01  2014/05 - ENG

 

 

 

 

 

Channel   

 

you can choose from 32 channels max available. 

 
Description 

 

Displayed tank description ex: DIESEL 01 

 
S.N. Address 

 

Unique serial number, each probe has one. 

 
Product 

select tank product type. 

 
Tot. Capacity 

 

Total capacity in liters, based on the loaded strapping table 

 
Tank height 

tank height in millimeters based in the loaded strapping table 

 
Offset 

Product float offset (-30000 +30000 mm): measurement unit in m, 1mm absolute resolution. Used to align 
the value of the height of the float of the tank product in the tank. 

 
Zero Water 

Water float offset (30000 mm): measurement unit in m, 1mm absolute resolution, under the specified value 
the height water value read by the float is zero.  

 
 

ALARM DEFINITION 

 

In the alarm section you set various alarm thresholds point for each level probe. 
 
Allarme HH 

very high threshold in mm. 

 
Allarme H 

high threshold in mm. 

 
Allarme L  

low threshold in mm. 

 
Allarme LL    

very low threshold in mm. 

 
Allarme Acqua 

water threshold in mm. 

 
 

TANK LEVELS 

 

Here you can see the current level of the product in the selected tank 
 
Product (mm) 

 

Product tank level. 

 
Water (mm) 

 

Water tank level. 

 
Temperature (C°)   

Product temperature in the tank 

 
 

RELAY DEFINITION 

Here you can assign relay functions from 1 to 16 for each tank. Relay can be assigned one for each tank or simultaniusly on all channels 
 
EX:  
Relay N1 Low level alarm tank 1   
Relay N2 Low level alarm tank 1   
 
Relay N1 Low level alarm tank 1 ,2,3…32 
 

WRITE DATA TO UNIT  

This button is used to store data 

Содержание Digimon TFT

Страница 1: ...Digimon TFT rev 01 2014 05 ENG 1 INSTALLATION MANUAL DIGIMON TFT CONSOLE ...

Страница 2: ...SCRIPTION 4 CONNECTION BOARD 4 CONNECTIONS PROSPECT 5 CPU BOARD 6 INSTALLATION 7 PROGRAMMING 8 ALARM DEFINITION 9 TANK LEVELS 9 RELAY DEFINITION 9 CHANNELS 10 SYSTEM CONFIGURATION 10 STRAPPING TABLE 10 DIGIMON FUCNTIONS 10 ATEX CERTIFICATION AND CESI NOTIFICATION 12 REVISION INDEX 23 ...

Страница 3: ...pment The manufacture is not responsible of any operation performed not mentioned in this handbook In case of failure or faulty operations please refer to authorized people in charge for maintenance or directly to the manufacturer The manufacturer refuses all responsibility for any eventual injury and or damage to things caused by the missing observation of safety requirements The assigned personn...

Страница 4: ...Vcc 2A Serial comunication RS485 Host comunication RS232 Configuration RS232 Working temperature 20 C 60 C Relative humidity Da 5 a 95 no humidity Protection IP66 68 Enclosure Painted metal Dimension mm 165 x 145 x 120 CONNECTION BOARD Follow these steps 1 Open the top enclosure 2 Remove the 4 cross head screw using correct screw driver that fixes the CPU board 3 Lift the CPU board WARNING be care...

Страница 5: ...RS485 B Brown 2 RS485 A 3 RS485 A Blu 3 RS485 B 4 GND White 4 GND CN4 RS232 SUB D 9 CN7 RS232 CPU 1 RS232 TX 2 RS232 RX 2 RS232 RX 3 RS232 TX 3 GND 5 GND CN7 Relay K1 contacts CN8 Relay K2 contacts 1 K1 NO 1 K2 NO 2 K1 Common 2 K2 Common 3 K1 NC 3 K2 NC CN9 Relay K3 contacts CN10 Relay K4 contacts 1 K3 NO 1 K4 NO 2 K3 Common 2 K4 Common 3 K3 NC 3 K4 NC ...

Страница 6: ...Digimon TFT rev 01 2014 05 ENG 6 CPU BOARD CPU board manages all console functions ...

Страница 7: ...emperature humidy and so on to avoid demages on the electric part Installation procedure Place the console on the wall fixed it with holes as described in the picture below Elettronic connection Follow the steps to connet the console elettrically Turn off all the power switches of the elettrical panel Connect power supply panel to thr consoleusing proper connectors To connect driving force please ...

Страница 8: ... rev 01 2014 05 ENG 8 PROGRAMMING Use Console Config software to program Digimon TFT console Select comunication port used to connect to the console The program now should look like this CONSOLE CONNECTED CORECTLY ...

Страница 9: ...r the specified value the height water value read by the float is zero ALARM DEFINITION In the alarm section you set various alarm thresholds point for each level probe Allarme HH very high threshold in mm Allarme H high threshold in mm Allarme L low threshold in mm Allarme LL very low threshold in mm Allarme Acqua water threshold in mm TANK LEVELS Here you can see the current level of the product...

Страница 10: ... interpolation between two near points In order to do that operation the strapping table correspondence mm lt must be downloaded into the console It is necessary to follow few rules in order to download correctly the table into the console Values in millimeters inches and liters gallons Maximum number of points 250 Numbers with decimals have to be written with a dot and not with a comma Table has ...

Страница 11: ...Digimon TFT rev 01 2014 05 ENG 11 Tank data Diagnostic Data Percentage tank data Graphical tank data ...

Страница 12: ...Digimon TFT rev 01 2014 05 ENG 12 ATEX CERTIFICATION AND CESI NOTIFICATION ...

Страница 13: ...Digimon TFT rev 01 2014 05 ENG 13 ...

Страница 14: ...Digimon TFT rev 01 2014 05 ENG 14 ...

Страница 15: ...Digimon TFT rev 01 2014 05 ENG 15 ...

Страница 16: ...Digimon TFT rev 01 2014 05 ENG 16 ...

Страница 17: ...Digimon TFT rev 01 2014 05 ENG 17 ...

Страница 18: ...Digimon TFT rev 01 2014 05 ENG 18 ...

Страница 19: ...Digimon TFT rev 01 2014 05 ENG 19 ...

Страница 20: ...Digimon TFT rev 01 2014 05 ENG 20 ...

Страница 21: ...Digimon TFT rev 01 2014 05 ENG 21 ...

Страница 22: ...Digimon TFT rev 01 2014 05 ENG 22 ...

Страница 23: ...Digimon TFT rev 01 2014 05 ENG 23 REVISION INDEX DATE REVISION NUMBER DESCRIPTION Firmware revision 05 2014 1 General revision ...

Страница 24: ...Start Italiana S r l Via Pola 6 20813 Bovisio Masciago MB Tel 39 0362 1581465 Fax 39 0362 1581464 www startitaliana it ...

Отзывы: