2.6

Firing Displays

This is shown when a delayed start is in progress.  The display
shows the hours:minutes remaining until firing commences.

This shows that the initial ramp, ramp 1 is being fired.  For addi-
tional information press the 

Æ

 key.  This additional information

is also displayed once per minute.

This shows that the final ramp, ramp 2 is being fired.  Press the

Æ

 key for additional information.

This shows that the controller is soaking.  Press the 

Æ

 key for

additional information including the time left in soak.

This shows that the soak period is complete and that the load is
cooling naturally.  

HOT!

 is displayed flashing.

This shows that the load has cooled to less than 100°C.

This shows that the load has cooled to less than 40°C & firing is
complete.

DELAYED START...
TIME LEFT  04:32

SLOW HEATING...

à

KILN TEMP       23°C

FAST HEATING...

à

KILN TEMP      800°C

SOAKING...

à

KILN TEMP   1200°C

COOLING...   HOT!
KILN TEMP   1172°C

COOL
KILN TEMP     96°C

          READY

SPS5.2 Manual

       Page 7

3.0

Installation Instructions

3.1

Safety

2.7

Power Fail Recovery

In the event of power failure followed by power restoration, the instrument attempts to take
intelligent recovery actions to avoid a firing being aborted.  The instrument has no direct
knowledge of how long the power has been off so the recovery action taken depends on where the
instrument had reached in the firing sequence prior to power failure as detailed below:-

Before Power Failure

After Power Failure

In 

READY

 mode

Timing delayed start

On Ramp 1 approaching t1

On Ramp 2 approaching t2

In Soak Period timing Soak
Time

Cooling after SOAK period

In 

READY

 mode

Immediate start as if the end of Delay Time reached

Immediate restart.  Temperature will increase at ramp rate
1 of the current program starting at the present temperature

Immediate restart.  If present temperature greater than t1
temperature will increase at ramp rate 2 of the current
programme starting at the present temperature.  If present
temperature is less than t1 temperature will increase at
ramp rate 1 of the current program starting at the present
temperature

As above.  The full soak period of the current program will
be re-applied

Cooling continued.

ISOLATE

BEFORE

REMOVING

COVER

Installation Category: II
Pollution Class: 2

WARNING

                    

ISOLATE FROM ELECTRICAL SUPPLY BEFORE OPENING THIS
INSTRUMENT FOR INSTALLATION, CONFIGURATION OR REPAIR
PURPOSES

230V ~ 50HZ 1.0A

Fuse: 1.0A Anti-surge
Wickmann type TR5 T1A 250V