4.0

Error Displays

Thermocouple burn-out is indicated by this display.  This indicates that the

thermocouple has become open circuit.  The
controller detects this condition while firing and
when in 

READY

 mode.  The controller will lock up

in this condition with the heater power off. The only
way to reset the controller from this condition is to

turn off the power, clear the fault and then turn the power to the instrument back on.

To clear the fault the thermocouple and associated wiring should be tested for open
circuits.  If the thermocouple is open circuit it will need to be replaced.

Heater failure or thermocouple short circuit is indicated by this display.  The

instrument detects this condition only in RUN mode
when heating power has been applied continuously
for 15 minutes but the temperature has increased by
less than 2ºC.  This indicates either that the wiring to
the thermocouple is short circuited or (more likely)

that one or more of the heater elements has failed and the heater is incapable of
reaching the required temperature.  The only way to reset the controller from this
condition is to turn off the power, clear the fault and then turn the power to the
instrument back on.

The controller performs continuous checks of its circuitry and embedded software to
check for potential error conditions.  If such an error is detected the control relay is

switched off and an error message is displayed  for
one minute.  After this period the controller resets
itself and restarts as if a power failure had occurred.
If the potential error has cleared the instrument will
proceed as normal.  If the error condition persists the

instrument will repeat the error display cycle.

In the event of an error contact the supplier quoting the error number.

  THERMOCOUPLE
   OPEN CIRCUIT!

  THERMOCOUPLE
   SHORT CIRCUIT!

        ERROR 7!

SPS5.1 Manual

       Page 3

1.0

Features

• 

Simple to use

• 

Large clear illuminated alphabetic display

• 

2 Temperature break points (0-1310°C)

• 

Ramp rate control (20-240°C/hour)

• 

Start delay (0-99hr 59min)

• 

User settings stored in non-volatile memory

• 

Intelligent power fail recovery

• 

Thermocouple failure detection

• 

Heater element failure detection

• 

R, K, N & S type thermocouple selection

2.0

Operating Instructions

2.1

Power On

When power is applied to the controller the display will illuminate & show the model number, version
number & the thermocouple type in use.  

READY

 will normally

1

 be displayed.  The heating power is off and

the controller is ready to accept keyboard commands.

1

If the display does not show 

READY 

then the instrument is in RUN mode because the previous firing

sequence was interrupted by a power failure - the controller is now trying to complete this interrupted
firing sequence.  To return to READY mode, if required, press the 

RUN/HALT

 key.

2.2

Instrument Capabilities

General

             

A typical firing sequence is illustrated below:-

Temperature ºC

ramp 1 rate
variable

ambient

Delay
Time

t1

Ramp 1

soak temperature

energy=100%

Ramp 2

Cooling

Soak
time

Содержание SPS5.1

Страница 1: ...oller RUN HALT SET SPS 5 1 Stanton Pottery Supplies Ltd Canal Lane Westport Lake Tunstall STOKE ON TRENT Staffordshire England ST6 4NZ Tel 44 0 1782 835467 Fax 44 0 1782 812435 email sales stanton kilns co uk www stanton kilns co uk Issue 5 1E01 Date 10 July 98 Stanton Pottery Supplies Ltd Manufactured in Staffordshire U K ...

Страница 2: ... wire size 1 5mm Temperature Ramp Rate to temperature t1 setting Range 20 to 240 C hour Resolution 20 C hour t1 setting Range 0 to 1310ºC Resolution 1ºC t2 setting Trim Range 0 to1310ºC Resolution 1ºC START DELAY setting Range 00 00 to 99hr 59min Resolution 1 min Control Accuracy Reading accuracy 0 25 FSD 1 digit P I D Control Cold junction compensation Environmental Operating temperature range 0 ...

Страница 3: ...is switched off and an error message is displayed for one minute After this period the controller resets itself and restarts as if a power failure had occurred If the potential error has cleared the instrument will proceed as normal If the error condition persists the instrument will repeat the error display cycle In the event of an error contact the supplier quoting the error number THERMOCOUPLE ...

Страница 4: ...rs which have been previously selected with the SET key Pressing this key when a firing in in progress will immediately abort the firing Pressing this key when READY is displayed enables the user to select firing parameters Pressing this key during a firing has no effect This is used to increment user input when in SET mode Pressing this key has no effect when READY is displayed or when a firing i...

Страница 5: ...S5 1 K4 is Mains Live input K5 is Mains Neutral input K6 is Earth input an Earth must be fitted to this controller VR1 is the display contrast control FS1 is the protective fuse 1 0A Anti surge Wickmann type TR5 T1A 250V Farnell Electronic Components 150 988 RS Components 226 6583 SPS5 1 Manual Page 5 2 4 Setting Pressing the SET key when READY is displayed causes the cur rently selected ramp rate...

Страница 6: ...actions to avoid a firing being aborted The instrument has no direct knowledge of how long the power has been off so the recovery action taken depends on where the instrument had reached in the firing sequence prior to power failure as detailed below Before Power Failure After Power Failure In READY mode Timing delayed start On Ramp 1 approaching t1 On Ramp 2 approaching t2 In Soak Period timing S...

Отзывы: