45
b) 3N ~ 400V / 50 Hz on the connecting terminals L1, L2, L3, N and PE ( ).
Connecting terminals of the supply cable
X1
L3
N
L2
L1
N
L1
/
/
Terminals L1, L2, L3 (3 x black or
black, grey, brown cable)
Terminal N (blue cable)
Terminal PE ( ) (yellow-green cable)
Input fuse: 3x16A
4.5.7 Connecting terminals of the communication cable
The communication cable is intended for the communication between the control unit TT3000 and
external device. For the dimensions of the communication cable, see technical data
Error! Reference
source not found.
CAUTION
It is important to correctly connect the connecting terminals X5 and X7.
In the case of WSL141 and WSL142
The communication cable connects the external device to the terminal terminal
X5
on the internal
device. It is necessary to connect the terminals
BUS–A
,
BUS–B
,
GND and 10 V.
X5
BUS-B
BUS-A
GND
10 V
DANGER
The communication connection is considered as a low-voltage connection. The type of the
communication cable must be H05VV-F 4 x 0.75mm2 (IEC 60227-53) or similar.
In the case of a prefabricated FTP cable, connect cable
1, 2
to
BUS – A
,
2, 3
to
BUS – B
and
GND
to
7, 8.