background image

8

4.

Fit the flue blanking plate to the top outlet 
connection using the nuts & bolts and place 
the top outlet blanking plate in position on the 
hob - see Fig 6.

5.

Fit the flue spigot to the back outlet 
connection.

Fig.5

Fig.6

Flue Blanking Plate

DOWN DRAUGHTS

However well designed constructed and positioned,
the satisfactory performance of the flue can be
adversely affected by down draught caused by near-
by hills, adjacent tall buildings or trees. These can
deflect wind to blow directly down the flue or create
a zone of low pressure over the terminal.

A suitable terminal or cowl will usually effectively
combat direct down blow but no cowl is likely to pre-
vent down draught due to a low pressure zone.
(See Fig.7)

Direction of wind

Pressure zone

Direction of wind

Suction zone

Pressure zone

Direction of wind

Suction zone

Pressure zone

Suction zone

Fig.7

VENTILATION & COMBUSTION AIR REQUIRE-
MENTS

It is imperative that there is sufficient air supply to
the stove in order to support correct combustion.
The air supply to this appliance must comply with
current Building Regulations Part J, Heat Providing
Appliances.  If another appliance is fitted in an adja-
cent room it will be necessary to calculate an addi-
tional air supply.

The minimum effective air requirement for this appli-
ance is 33cm². When calculating combustion air
requirements for this appliance use the following
equation:

550mm² per each kw of rated output above 5kw
should be provided, where a flue draught stabiliser is
used the total free area shall be increased by
300mm² for each kw of rated output.

Содержание Solis F1100 Panoramic

Страница 1: ...hould be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where children...

Страница 2: ...n HRV 9 13 Location 10 14 Clearances To Combustibles 10 15 Floor Protection 10 16 Stove Dimensions 11 17 Commissioning and Handover 11 18 Operation 11 19 Air Controls 11 20 Recommended Fuels 12 21 Tec...

Страница 3: ...Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufacturing defect that fails within the warranty period unde...

Страница 4: ...be provided to the chimney serving the appliance to allow for cleaning 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Loca...

Страница 5: ...flue ways of the stove weekly and ensure that there are no blockages Check flueways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of...

Страница 6: ...ications may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys Your Solis stove is supplied with t...

Страница 7: ...ned through the stove it is necessary to provide a soot box access door in the flue for cleaning See Fig 2 for recommended locations The stove comes configured for a Top Outlet Flue connection and can...

Страница 8: ...a low pressure zone See Fig 7 Direction of wind Pressure zone Direction of wind Suction zone Pressure zone Direction of wind Suction zone Pressure zone Suction zone Fig 7 VENTILATION COMBUSTION AIR R...

Страница 9: ...air permeability is less than 5m3 h m2 nor mally newer properties built from 2006 then a per manent ventilation must be fitted to provide 550mm2 of ventilation for each kW of rated output If a draugh...

Страница 10: ...mm 31 1 2 From the back 130 mm 5 From the sides 700 mm 27 1 2 From the flue pipe 460 mm 18 straight up only It is recommended that the appliance is sited next to and on a non combustible surface A min...

Страница 11: ...ct use of the appliance and warn them to use only WOOD Advise the user what to do should smoke or fumes be emitted from the stove The customer should be warned to use a fireguard to BS 8423 2010 in th...

Страница 12: ...l kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Keep all such liquid well away from the heater at all times Operate the stove only with the fuelling d...

Страница 13: ...urn fill the firebox of fuel up to the maximum height just below the top of the fire fence at the front of the door opening Close the pri mary secondary air control fully DISPOSAL OF ASHES Your stove...

Страница 14: ...additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Part J Further guidance on the installation of a carbon monoxide alar...

Страница 15: ...TECTION PLATE 30008595 9 LH PROTECTION PLATE 30000415 10 RH PROTECTION PLATE 30008617 11 FLUE SPIGOT 30000201 12 TOP PLATE 30008618 13 SIDE PANEL 30008619 15 FIRE DOOR 30009492 16 BACK BRICK H00236AXX...

Страница 16: ...16 Supplied by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Item No N00785AXX Rev 001 SG260518...

Отзывы: