© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
203959
Rev. F, 10/2/02
12 of 23
WARNING
To prevent injury to personnel and damage to equipment, the following settings must be made
before
applying power to control box.
4.1.2
SET potentiometers and switches to initial positions as follows:
a.
SET stall speed potentiometer to full clockwise (maximum) position.
b.
SET torque potentiometer to full clockwise (maximum) position.
c.
SET high/low range DIP switch S1 as applicable:
WARNING
When changing from low range to high range, the door will move faster.
CAUTION
To ensure proper operation of door, DIP switch S1 must be set to "H" (high range) on
all
full-energy, dual
operator, Magic-Swing and bifold applications.
•
IF single-operator full-energy application, dual-operator application, Magic-
Swing application, or bifold application, SET to "H" (high range).
•
IF single-operator low-energy application, SET to "L" (low range).
d.
SET open speed potentiometer as applicable:
•
IF high/low range DIP switch S1 is set to ON (high-speed range), SET open
speed potentiometer to midrange position.
•
IF high/low range DIP switch S1 is set to “OFF” (low-speed range), SET
open speed potentiometer to maximum (full clockwise) position.
e.
SET open check speed potentiometer to
3
/
4
of full clockwise position.
f.
SET time delay potentiometer to full counterclockwise (minimum) position.
g.
SET Magic-Touch
time delay rotary switch S4 to 0 (5 seconds).
h.
SET "CLS" (close speed) rheostat to midrange position.
i.
IF application is a Magic-Force installation, SET “CK” (close check speed) rheostat
to full counterclockwise position.
4.1.3
Refer to Attachment 8, and PERFORM tune-in as applicable.
4.2
Final Tune-In Adjustments
4.2.1
ENSURE door-opening path is clear of all wires and obstructions.
4.2.2
SET “ON/OFF/HOLD OPEN” switch to “OFF.”
4.2.3
CONNECT power pigtail assembly.
4.2.4
Refer to ANSI A156.10, "American National Standard for Power Operated Doors" or
ANSI 156.19, “American National Standard for Power Assist and Low Energy Power
Operated Doors,” and DETERMINE ANSI door operating requirements.
4.2.5
CYCLE and RECYCLE door several times to verify proper speeds and forces, and
PERFORM adjustments in the following order:
a.
ADJUST close check cam.
b.
ADJUST open speed potentiometer.