Table 1. Minimum approach distances from energized conductors for qualified line-clearance arborists and
qualified line-clearance arborist trainees.
Nominal
Voltage
kV phase-to-phase
Includes 1910.269
elevation factor, sea
level to 5000 ft
1
)
Includes 1910.269
elevation factor,
5001–10,000 ft
1
)
Includes 1910.269
elevation factor,
10,000–14,000 ft
1
)
ft-in
m
ft-in
m
ft-in
m
0.05–1.0
Avoid contact
Avoid contact
Avoid contact
1.1–15.0
2-04
0.71
2-08
0.81
2-10
0.86
15.1–36.0
2-09
0.84
3-02
0.97
3-05
1.04
36.1–46.0
3-00
0.92
3-05
1.04
3-09
1.14
46.1–72.5
3-09
1.14
4-03
1.30
4-07
1.40
72.6–121.0
4-06
1.37
5-02
1.58
5-07
1.70
138.0–145.0
5-02
1.58
5-11
1.80
6-05
1.96
161.0–169.0
6-00
1.83
6-10
2.08
7-05
2.26
230.0–242.0
7-11
2.41
9-00
2.75
9-09
2.97
345.0–362.0
13-02
4.02
15-00
4.58
16-03
4.96
500.0–550.0
19-00
5.80
21-09
6.63
23-06
7.17
765.0–800.0
27-04
8.34
31-03
9.53
33-10
10.32
1)
Exceeds phase-to-ground; elevation factor per 29 CFR 1910.269.
Table 2. Minimum approach distances to energized conductors for persons other than qualified line-clear
-
ance arborists and qualified line-clearance arborist trainees.
Nominal Voltage
kV phase-to-phase
1)
Distance
ft-in
m
0.0–1.0
10-00
3.05
1.1–15.0
10-00
3.05
15.1–36.0
10-00
3.05
36.1–50.0
10-00
3.05
50.1–72.5
10-09
3.28
72.6–121.0
12-04
3.76
138.0–145.0
13-02
4.00
161.0–169.0
14-00
4.24
230.0–242.0
16-05
4.97
345.0–362.0
20-05
6.17
500.0–550.0
26-08
8.05
785.0–800.0
35-00
10.55
1)
Exceeds phase-to-ground.
ELECTRICAL HAZARDS