T15e Tag Deployment & User Guide
51
Configuring an Automatic Dismiss Door Open Event
This event will automatically dismiss the Door Open Event once the door is
closed.
Create a Sensor Monitor Event according to the following:
1.
Select Sensor Monitor Event.
Add a new Sensor Monitor Event and name the event accordingly,
such as Auto Dismiss Open Door Alert.
Set Priority to Medium.
Set the Reset Interval to 300.
Under Subscribers, subscribe to the correct category.
2.
Under Event Conditions, select the Sensor Type as Contact Sensor.
3.
Set 'Sensor Level is = ‘1' -. This value triggers an event when the door
is closed.
Only trigger after: Set this to ‘0’. This means the event will be
triggered immediately once the door is closed.
Optional: Remind me every: Once an alert has been dismissed, this
setting can be used to check if the condition still persists and trigger an
alarm every X minutes. The alert is generated during the next tx
Interval. This setting should be used if a long tx interval has been set
for the tag and where responding to alerts is time sensitive.