FITTING AND OPERATING

SUMMARY OF AVR CONTROLS

CONTROL

FUNCTION

DIRECTION

VOLTS

TO ADJUST GENERATOR OUTPUT VOLTAGE

CLOCKWISE INCREASES OUTPUT VOLTAGE

STABILITY

TO PREVENT VOLTAGE HUNTING

CLOCKWISE INCREASES STABILITY OR DAMPING EFFECT

STABILITY SELECTION

TO OPTIMISE TRANSIENT PERFORMANCE

LINK DEPENDING UPON KW OUTPUT

UFRO

TO SET UNDER FREQUENCY ROLL OFF KNEE POINT

CLOCKWISE REDUCES THE KNEE POINT FREQUENCY

FREQUENCY SELECTION

TO SELECT ‘UFRO’ CONTROL RANGE

LINK DEPENDING ON OPERATING FREQUENCY

DROOP

TO SET GENERATOR DROOP TO 5% AT FULL LOAD 0 PF

CLOCKWISE INCREASES THE DROOP

TRIM

TO MATCH AVR INPUT

CLOCKWISE ALLOWS THE ACCESSORY MORE CONTROL OVER AVR

DIP

TO SET THE INTIAL FREQUENCY RELATED VOLTAGE DIP

CLOCKWISE INCREASES THE VOLTAGE DIP

OVER/V

TO SET THE OVERVOLTAGE PROTECTION CUT OFF LEVEL

CLOCKWISE INCREASES THE OVERVOLTAGE CUT OFF LEVEL

RMS

SET AND SEALED AT FACTORY

The AVR is fully encapsulated to ensure long trouble-free
operation. It is usually fitted on a panel of the terminal box. It
can also be separately fitted in a switchboard.

ADJUSTMENT OF AVR CONTROLS

VOLTAGE ADJUSTMENT

The generator output voltage is set at the factory, but can be
altered by careful adjustment of the volts control on the AVR
board, or by the external hand trimmer if fitted. Terminals 1 &
2 on the auxiliary terminal block inside the generator terminal
box will be fitted with a shorting link if no hand trimmer is
required.

Do  not  increase  the  voltage  above  the

rated  generator  voltage.  If  in  doubt,  refer

to  the  rating  plate  mounted  on  the

generator case.

If a replacement AVR has been fitted or re-setting of the
VOLTS adjustment is required, proceed as follows:-

1)  Before running generator, turn VOLTS control fully anti-

clockwise.

2)  Turn remote volts trimmer (if fitted) to midway position.

3)  Turn STABILITY control to midway position.

4)  Connect a suitable voltmeter (0-300V ac) across line to

neutral of the generator.

5)  Start generator set, and run on no load at nominal

frequency e.g. 50-53Hz or 60-63Hz.

6)  If the red Light Emitting Diode (LED) is illuminated, refer

to the Under Frequency Roll Off (UFRO) adjustment.

7)  Carefully turn VOLTS control clockwise until rated voltage

is reached.

8)  If instability is present at rated voltage, refer to stability

adjustment, then re-adjust voltage if necessary.

9)  Voltage adjustment is now completed.

STABILITY SELECTION

The "jumper" selector lead should be correctly linked for the
frame size of the generator (See diagram above).