SolConeX extra-low voltage coupling
Series 8573/14
7.2
Mounting / Dismounting, Operating Position
7.2.1 Assembly
This device is suitable for outdoor and indoor use.
Operating position
• Store in an unplugged state, suspended with the contacts pointing downward.
7.3
Installation
DANGER
Explosion hazard due to insufficient protective measures!
Non-compliance results in severe or fatal injuries.
• Select suitable cables to ensure that the maximum permissible
conductor temperatures are not exceeded.
• When using core end sleeves, attach them using a suitable tool.
• Use only separately tested cable entries and stopping plugs with
an EU Type Examination Certificate.
• The conductor insulation must be touching the terminal.
• Do not damage the conductor (e.g. nicking) when stripping it.
• Always connect the protective conductor.
DANGER
Explosion hazard in the case of installation in special areas with
potentially explosive dust!
Non-compliance results in severe or fatal injuries.
• Do not use the device in areas where there are processes
generating strong charges, machine friction processes,
separation processes and electrospray processes
(e.g. around electrostatic coating systems) and pneumatically
generated dust.
Two conductors can be installed under one connection terminal.
Material and cross section of both conductors must be identical.
The conductors can be connected without any special preparations.