CPU module for Zone 2 / Division 2
Series 9442/35
Diagnostic and
parameterisation
Functions
• Use the web server or IS1+ detect software to set the IP address
(for Ethernet)
• Web server
• Load or read back configuration data and parameters in the IS1+ field
stations
• Read inputs
• Read and write outputs
• Transmit diagnostics data
(e.g. configuration error, hardware error, signal error)
• Transmit HART commands from/to HART field devices
• Firmware downloads using the web server
Retrievable
parameters
Manufacturer, type, hardware revision, software revision, serial number
Connectable
software packages
• IS Wizard (using the USB ServiceBus)
• R. STAHL DTM devices with FDT frames
(e.g. FDT container by M+M; PACTware)
• AMS by Emerson Process Management
• PDM by Siemens
• PRM and Fieldmate by Yokogawa
• FieldCare by E Hauser
• FDM by Honeywell
Galvanic separation
Test voltage
acc. to standard
EN 60079-11
Between the
auxiliary power
and CPU
)
1500 V AC
Between 2 CPUs
(redundancy)
)
1500 V AC
Electromagnetic
compatibility
Tested to the following standards and regulations:
EN 61326-1 (2013) IEC 61000-4-1 to 61000-4-6, NAMUR NE 21
Ambient conditions
Ambient temperature
Storage temperature
-40 to +80 °C
Maximum relative
humidity
95 % (without condensation)
Technical Data
-40 to +65 °C:
Mounting on a BusRail (DIN mounting rail)
without mounting plate
-40 to +70 °C:
Mounting on a BusRail (DIN mounting rail)
and on a galvanised, sheet steel mounting plate of
at least 3 mm using four additional safety screws
-40 to +75 °C:
Mounting on a BusRail (DIN mounting rail)
and on a coated, aluminium mounting plate of
at least 6 mm using four additional safety screws
(EN-AW6082 or comparable heat conductivity)