7.4
Installation Conditions for Electrical Connections
Cable entry to device
7.5
Access to the PCB
Instructions
- Remove socket head screws x 6
- Lift strobe assembly and disconnect upper and lower PCB’s
- Set aside strobe assembly and upper PCB and terminal to lower PCB
WARNING
No explosion protection if non-approved cable glands are used!
Only cable glands with a corresponding certificate may be used.
They must be flameproof (Ex d), suitable for the type of cable used and
fulfil the requirements of IEC/EN 60079-14.
Cable entry temperature may reach 70 °C.
To ensure the required ingress protection, installation of the cable gland
must be performed in accordance with the manufacturer's instructions.
For unused enclosure holes use Ex d stopping plugs, for unused cable
glands Ex d plugs. Make sure that these components have an appropriate
approval and fulfil the requirements of IEC/EN 60079-14.
All threaded cable entries to be fitted with an appropriately certified
component and the thread sealed with a suitable non-setting thread
sealant to maintain IP 66 rating.
15755E00
1 Socket head screws
2 Strobe assembly
3 Sealing O ring
4 Flash tube, attached to upper PCB
5 Cheese head screws
6 Lower PCB
7 Device base
Exploded diagram accessing the PCB FX15
1
2
3
4
5
6
7