Operating Instuctions
English
16 Resistance Isolator Type 9180
5.3
Engineering of the power dissipation in cabinets
When electronic devices are integrated in cabinets free air movement is restricted and the
temperature rises. To minimise the temperature rise it is important to optimise the power
dissipation as well as the elimination of the produced heat inside a cabinet.
a) Natural Convection in closed cabinets
Application: when the dissipated power is moderate and when the system operates in
a dusty or harsh environment
Calculation of the maximum allowed power dissipation:
Pmax =
t * S * K
P
max
[W]
max. allowed power dissipation in the cabinet
t [°C]
max. allowed temperature rise
S [m²]
free, heat emitting surface of the cabinet
K [(W/m²*°C)]
thermal emitting coefficient (K=5.5 for painted steel sheets)
The calculated value for P
max
has to be smaller than the total average power dissipation
(70 % of max. power dissipation) of the installed isolators: Pmax <
P
70%
b) Natural convection in open cabinets
Function: the heat is removed by cool air flowing through the devices
Requirements:
- inlet and outlet ports in the lower and upper ends of the cabinet
- the air flow path must be kept free from obstacles.
Result: Depending on the engineering the improvement can reach a
two times higher
power dissipation as with a)
c) Forced ventilation with heat exchanger in closed cabinets
Application: when either the harsh environment or the high dissipated power do not
allow natural convection
Function: a heat exchanger with a fan pulls the air into the cabinet and pushes it into the
heat exchanger plates that are cooled by the external ambient air moved by a second
fan.
Result: Depending on the engineering the improvement can reach a
5 or 6 times
higher
power dissipation as with a)
d) Forced ventilation in open cabinets
Function: the filtered air is taken from the bottom cabinet openings by one or more fans,
flows through the devices, and finally exits at the top of the cabinet.
Calculation of the required air flow:
Q = (3.1 * P
70%
) /
t
Q [m³/h]
required air flow
P
70%
[W]
dissipated power (70 % of max. power dissipation)
t [°C]
allowed temperature rise in the cabinet
e) Air conditioned cabinets
Application: for hot climates - it is possible to reach a cabinet temperature equal or even
lower than the ambient temperature
Function: a specific refrigerating system or the existing air conditioning system can be
used for cabinet conditioning
Содержание 9180
Страница 1: ...Typ Type 9180 Widerstandstrennübertrager Resistance Isolator Betriebsanleitung Operating Instruction ...
Страница 12: ......
Страница 22: ...22 EG Konformitätserklärung EC Declaration of Conformity ...
Страница 23: ...23 Certification drawing FM FMc ...