147234 / 8146655300
2018-08-16·BA00·III·en·03
Technical Data
9
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Motor Protection Circuit Breaker
Series 8146/5-V27
Switch insert
Electrical data
Rated operational
voltage
max. 690 V AC, 50/60Hz
Rated operational
current
0.1 to 22.5 A
Switching capacity Depending on the selected adjustment range (AC)
Service life
electrical
10
5
operating cycles
mechanical
10
5
operating cycles
Main contacts
3-pole
Short-circuit
protection
Technical Data
230 V
400 V
500 V
690 V
7.0 kW
12.4 kW
16 kW
22 kW
Adjustment
range up to
Highest rated current of the short circuit fuse if I
CC
> I
CS
230 V AC
400 V AC
500 V AC
690 V AC
I
CS
gG,
aM
I
CS
gG,
aM
I
CS
gG,
aM
I
CS
gG,
aM
kA
A
kA
A
kA
A
kA
A
0.16 A
0.25 A
0.40 A
0.63 A
1.00 A
1.60 A
2.50 A
40
10
4.00 A
60
16
10
16
6,30 A
75
25
40
25
3
25
9.00 A
65
32
30
32
3
32
12.50 A
75
40
55
40
25
40
3
40
16.00 A
65
50
40
50
20
50
2
50
20.00 A
55
63
25
63
15
63
2
50
22.50 A
50
63
15
63
15
63
2
50
I
CS
= rated short-circuit breaking capacity
I
CC
= projected short-circuit current at mounting location
Areas without specifications can be operated at up to 100 kA without a
pre-fuse.