![Stahl 6525 Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/stahl/6525-series/6525-series_operating-instructions-manual_1357761007.webp)
244627 / 652560300010
2017-07-13·BA00·III·en·03
Technical data
7
Floodlight LED
Series 6525
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
5
Technical data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx EPS 15.0032
Ex nR op is IIC T6 ... T5 Gc
Ex tb IIIC T80°C ... T95°C Db
Europe (ATEX)
Gas and dust
EPS 15 ATEX 1 991
E
II 3 G Ex nR op is IIC T6 ... T5 Gc
E
II 2D Ex tb IIIC T80°C ... T95°C Db
Certifications and certificates
Certificates
IECEx, ATEX, India (PESO)
Technical Data
Electrical data
Electronic balast
Rated voltage
220 ... 240 V, 50/60 Hz
Voltage range
198 ... 264 V, 50/60 Hz
Current
consumption
Inrush current
Power factor
> 0.95
at ambient temperature
Temperature class
6525/11..-....-....-...
-50 °C < T
amb
< +55 °C
T5 / T95 °C
6525/11..-21..-....-...
-50 °C < T
amb
< +50 °C
T6 / T80 °C
6525/11..-42..-....-...
-50 °C < T
amb
< +45 °C
T6 / T80 °C
6525/11..-2:
0.54 A
6525/11..-4:
0.94 A
6525/11..-21
(120 W Version)
6525/11..-42
(210 W Version)
I
peak
(measured at 50 % I
peak
)
58 A;
ã
t = 360
m
s
116 A;
ã
t = 360
m
s
max. light fittings per circuit breaker
Type B 10 A
4
2
Type B 16 A
9
4
Type B 25 A
20
10
Содержание 6525 Series
Страница 21: ......