Maintenance, Overhaul, Repair
18
251652 / 612560300010
2019-04-10·BA00·III·en·05
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Floodlight LED
Series 6125
9
Maintenance, Overhaul, Repair
9.1
Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
• Perform maintenance and repair work in accordance with IEC 60079-17 and
IEC 60079-19.
As a minimum, check the following points during maintenance work on the device:
• Whether the clamping screws holding the cables are securely seated
• Whether the device enclosure and/or protective enclosure have cracks or other visible
signs of damage
• Whether the seal shows signs of ageing or damage (completely replace enclosure
components with damaged foamed seal)
• Whether the device is clean inside and out
• Whether the permissible temperatures (in accordance with EN 60079) are complied
with
DANGER
Explosion hazard due to hot built-in components!
Non-compliance results in severe or fatal injuries.
• Only open the enclosure in switched-off state.
• The device must be allowed to cool down for at least 15 minutes before
opening it.
CAUTION
Risk of electric shock or malfunction of the device due to unauthorized work!
Non-compliance can result in light injuries!
• Before carrying out work on the device, switch off voltage supply.
• Work performed on the device must only be carried out by authorized
and appropriately trained qualified electricians.
NOTICE
Danger due to electrostatic discharge.
Electronic components can be destroyed if touched.
• Do not touch the LED-PCBs!
CAUTION
Danger of electric shock due to energised parts!
Non-compliance can result in minor injuries!
• All connections must be disconnected from the power supply.
• Secure the connections against unauthorized switching.
Observe the relevant national regulations in the country of use.