Stabila OLS 26 Скачать руководство пользователя страница 7

Measuring angles

2. Align the level with point A.
3. Set the horizontal circle to “0“.
4. Align the level with point B.
5. Read off the horizontal angle between 

    point A and point B from the horizontal circle

Check the reticle 

1.  Set up the instrument and level it 

     between 2 levelling rods 

     (approximately 30m from each).
2. Align the instrument with measuring 

     point A and read off the figure A1 on 

     the measuring point.

∆h1 = A1-B1

Difference in height between the measuring points:

3. Align the instrument with measuring 

     point B and read off the figure B1 on 

     the measuring point.

A1

A

B

∆h1

B1

2,218 m

Example:

1,950 m

Example: ∆h1 = 2,218 m - 1,950 m = 0,268 m

Checking the calibration

The OLS 26 level is designed for use on construction sites and was perfectly 

adjusted when it left our factory. As with any precision instrument, however, 

its calibration must be regularly checked. The unit should be checked before 

starting any new tasks, particularly when the unit has been exposed to strong 

vibrations. After an impact, the unit should be checked throughout its whole 

self-levelling range. 

1. Use the plumb-line to position the 

     level exactly over the angular point.

A

B

Example:  80°

A

B

Содержание OLS 26

Страница 1: ...Operating instructions OLS 26 en 2018...

Страница 2: ...B1 B2 B3...

Страница 3: ...1 2 3 4 1 5 7 8 9 12 10 11 2 A 6...

Страница 4: ...Like every precision optical instrument the OLS 26 must be handled with great care Its accuracy should be checked carefully before each occasion on which it is used 12 5 8 threaded connector for tripo...

Страница 5: ...is in exactly the right position suspend the plumb line from the connecting screw under the instrument if necessary Setting up the telescope 1 Focussing the eye piece Turn the OLS 26 to face a light c...

Страница 6: ...el the instrument 2 Align the level with measuring point A and read off the figure A1 3 Align the level with measuring point B and read off figure B1 h A1 B1 Example h 2 218 m 1 950 m 0 268 m Measurin...

Страница 7: ...instrument with measuring point B and read off the figure B1 on the measuring point A1 A B h1 B1 2 218 m Example 1 950 m Example h1 2 218 m 1 950 m 0 268 m Checking the calibration The OLS 26 level is...

Страница 8: ...ed earlier coincide 5 Screw the cover 11 back into place h2 A2 B2 X 0 0001 Adjust the reticle 2 007 m 1 753 m 0 254 m Difference in height between the measuring points The error in the height is calcu...

Страница 9: ...to which the purchaser is entitled and which are not limited by this guarantee STABILA guarantees the instrument against defects and the absence of the warranted characteristics resulting from materia...

Отзывы: