User Manual
Modbus TCP/EtherNet IP Gateway
GT200-MT-EI
WWW.SSTCOMM.COM
44
In the new pop-up window, it needs to configure as below:
Message Type: CIP Generic
Service Type: Select “Set Attribute Single”, now, relevant Service Code will become “10 (Hex)”
Class: 4 (Hex)
Instance: 101
Attribute: 3 (Hex)
Source Element: Select “WriteData” tag, it indicates the data in the “WriteData” tag will become the data
PLC outputs.