Release  the  spring  pin  and  clip  the  transmitter  on  the 

mounting rail. 

1.2 Screw mounting method: 

3mm  diameter  hole  in  the  fixed  plate  according  to  the  screw 

hole position shown in Fig. 3; 

Use the screw 

Φ

3 to insert into hole and secure it. 

2  Products  factory  has  been  accurately  set  according  to  the 

"product  standard".  Apply  power  after  determine  the  correct 

wiring. 

3

 

The  maximum  wire  diameter  of  the  terminal  block  is  2mm 

(16-26AWG). Remove the 4mm  ~ 5mm insulation layer  from the 

end of the mounting wire and insert it into the terminal block, then 

tighten the screw. 

4 Product supply power requires the isolation voltage 

 2000VAC, 

AC ripple <10mV. Multiple transducers can share a common set of 

power  supplies,  but  the  power  circuit  can  no  longer  be  used  to 

drive  relays  and  other  can  produce  spikes  in  the  load,  in  order  to 

avoid interference signal transmission to the transducer. 

5

 T

he transducers output 0-20mA (or 4-20mA), the RL standard is 

  250

Ω

,  and  0-5V  voltage  output  RL  standard  is 

  2K

Ω

,  can 

guarantee  the  output  accuracy  and  linearity  over  the  entire  rated 

input range. 

8 Example of product accuracy level verification 

1  According  to  the  definition  of  the  transducer  terminal,  connect 

the test circuit as shown. 

 

 

 

 

 

 

Figure 4, voltage output product accuracy test wiring diagram 

 

 

 

 

 

 

 

 

Figure 5, current output product accuracy test wiring diagram 

Note:

 The voltage output measured with the Vo table, the current 

output measured with the Io table; 

2 The test shall be carried out under the following environmental 

conditions: 

Ø

 

Power supply: nominal 

±

 5%, ripple 

 10mV; 

Ø

 

Ambient temperature: 25 

 

±

 5

°

C

Ø

 

Relative humidity: RH (45 ~ 80)%; 

Ø

 

The accuracy is 0.05 above of the signal source and                 

measurement instrument. 

3Power preheat 2min; 

4 Voltage V input and monitoring methods: 

A  high-precision  high-voltage  meter  calibrator  can  directly 

input  voltage  V,  and  record  the  meter  calibration  instrument 

display data. 

If there is no high-precision voltage meter calibrator, but there 

is  a  common  meter  calibrator,  use  high-precision  multi  meter 

to monitor the output voltage V of the common meter. 

5  Assuming  the  transmitter  input  is  0-300VAC,  the  output  is 

0-5VDC,  given  any  input  value  V  in  the  transducer  range,  the 

theoretical  output  value  (Vz)  of  the  transducer  is  calculated  as 

follows: 

Vz = V

÷

300

×

5V 

If the output is 0-10V, then Vd = V

÷

300

×

10V; 

If the output is 4-20mA, then Iy = 4+ V

÷

300

×

16mA; 

If the output is 0-20Ma, then Iz = V

÷

300

×

20mA. 

6

 

The monitoring table measures the DC voltage output value Vo 

or  the  current  output  value  Io  and  calculates  the  error  between  it 

and the standard value according to the following correspondence 

formula: 

Vo-Vz

│≤

25mV is normal, or excessive (0-5V output, 0.5); 

Vo-Vd

│≤

50mV is normal, or excessive (0-10 output, 0.5); 

Io-Iy

│≤

80uA is normal, or excessive (4-20mA output, 0.5); 

Io-Iz

│≤

100uA is normal, or excessive (0-20mA output, 0.5). 

7

 

Repeat 5 and 6 two operations,

 

the resulting error value of each 

point  in  each  phase  is  within  the  specified  accuracy  range,  the 

transducer accuracy level is qualified 

Note: 

and  other  technical  indicators  of  the  verification  method 

detailed consultation with our company. 

9 Notes 

1

 

Please pay attention to the wiring on product label and the 

output contact capacity. 

2  Transducer  for  the  integrated  structure,  not  removable,  and 

should avoid collision and fall. 

3

 

The  transducers  are  used  in  environments  with  strong 

electromagnetic      interference.  Standard  precaution  such  as 

shielding  the  input  and  /or  output  lines  should  be  observed.  All 

Power 

Supply   

Power   

Supply 