SRP WTH Series Скачать руководство пользователя страница 4

Series WTH 

 

 

 

                     Page 4 

 

 

 

 

 LT105 Feb. 2019    

Introduction  

 
Superior Radiant Products is a company in the infrared heating industry founded on the principles of product quality 
and customer commitment. 
Quality commitments are evidenced by superior design, a regard for design detail and an upgrade of materials 
wherever justifiable. 
Customer commitment is apparent through our ready responses to market demands and a never ending training 
and service support program for and through our distributor network. 
Superior Radiant offers its 20 years of infrared expertise in a cost effective unitary heater design as culmination of 
that commitment.  

Series

 

WTH

 models are field assembled, low intensity infrared heaters that are easy to install 

and maintain, and which were engineered with significant input from our customers. They are designed to provide 
economical operation and trouble-free service for years to come. 
 

 

Important 

 

These instructions, the layout drawing, local codes and ordinances, and applicable standards such as apply to gas 

piping and electrical wiring comprise the basic information needed to complete the installation, and must be 

thoroughly understood along with general building codes before proceeding. 

 

Only personnel who have been trained and understand all applicable codes should undertake the installation. SRP 

Representatives are Factory Certified in the service and application of this equipment and can be called on for 

helpful suggestions about installation. 

 

Installation Codes 

Installations must comply with local building codes, or in their absence, the latest edition of the national regulations 
and procedures as listed below. 

General Installation and Gas Codes 

Heaters must be installed only for use with the type of gas appearing on the rating plate, and the installation must 
conform to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 in the USA and CSA B149.1 and B149.2  
Installation Codes in Canada. 
This heater maybe approved for either indoor or outdoor installation. Not for use in residential dwellings, refer to 
Rating plate. 

Aircraft Hangar Installation 

Installation in aircraft hangars must conform to the Standard for Aircraft Hangars, ANSI/NFPA 409 in the USA and 
CSA B149.1 and B149.2 Installation Codes in Canada. 

Public Garage Installation 

Installation in public garages must conform to the Standard for Parking Structures, NFPA-88A or Standard for 
Repair Garages, NFPA 88B, in the USA and CSA B149.1 and B149.2 Installation Codes in Canada. 

Parking Structures 

Technical requirements are outlined in ANSI/NFPA 88B (USA) 
 

Содержание WTH Series

Страница 1: ...ce If you smell gas 1 Open windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call your gas supplier OWNER INSTALLER Retain this Manual ensure available for Service Im...

Страница 2: ...PLOSIONS HAZARD This heater is equipped with an automatic ignition device Do not attempt to light the burner by hand Failure to comply could result in a serious fire and personal injury hazard CAUTION...

Страница 3: ...ELD REFLECTOR INSTALLATION 22 INSTALLATION PREMIUM HEAT EXCHANGER 23 INSTALLATION SEQUENCE 23 HANGERS INSTALLATION 23 TUBE INSTALLATION 25 HEATER AND BAFFLE INSTALLATION 27 REFLECTOR INSTALLATION 29 E...

Страница 4: ...l building codes before proceeding Only personnel who have been trained and understand all applicable codes should undertake the installation SRP Representatives are Factory Certified in the service a...

Страница 5: ...must comply with all local requirements Venting Refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the USA and CSA B149 1 and B149 2 Installation Codes in Canada for proper location sizing an...

Страница 6: ...Series WTH Page 6 LT105 Feb 2019 Dimensional Charts Heat Exchanger Figure 1 Overall Dimensional Information Figure 2 Component Dimensional Information...

Страница 7: ...nless steel The following Special Configurations are also approved 80 000 BTU Hr 50 heat exchanger with no baffle or 6 aluminized baffle 100 000 BTU Hr 50 heat exchanger with no baffle or 6 aluminized...

Страница 8: ...d surfaces and other materials which maybe damaged by radiant or convective heat Combustible materials are considered to be wood compressed paper plant fibres plastics Plexiglas or other materials cap...

Страница 9: ...71 180 33 84 4 10 36 91 74 188 36 91 6 15 40 102 78 198 40 102 6 15 44 46 80 203 44 46 45 Reflector Tilt A B C D 4 10 4 10 40 102 38 97 4 10 4 10 50 127 46 117 4 10 4 10 58 147 50 127 4 10 4 10 67 170...

Страница 10: ...0 102 6 15 45 114 82 208 44 112 U Tube Opposite 45 A B C D 4 10 46 117 51 129 16 41 4 10 50 127 54 137 18 46 4 10 54 137 64 163 18 46 4 10 63 160 69 175 22 56 4 10 64 163 71 180 24 61 8 20 67 170 74 1...

Страница 11: ...tandard Heat Exchanger A general ordered sequence for installation is provided below for reference HANGERS INSTALLATION Suspension mechanism must allow for lateral tubing expansion A minimum 12 length...

Страница 12: ...n the chain with Quick Links or S hooks refer to Figure 4 Figure 5 Figure 5 Typical Hanging Points Place the first flanged aluminized tube in the first two hangers Figure 6 Be sure the flange is towar...

Страница 13: ...hanger for support and thereafter 1 hanger section The reflector brace should be installed 6 12 from burner Also the tube weld seam must face down refer to Figure 6 for more details Figure 6 Installat...

Страница 14: ...oupling liners tighten each of the coupling bands progressively and alternately Tightening one band completely before the other may result in an undesirable wrinkle in the liner refer to Figure 8 Be s...

Страница 15: ...on the baffle is folded over the end of the tube and clamped in place by the vent connector and vent system refer to Figure 10 Note Baffles are always placed at the end of the last heat exchanger tub...

Страница 16: ...ries WTH Page 16 LT105 Feb 2019 Figure 10 Baffle Installation A general overall view of the tubes and reflector hangers are shown in Figure 11 below Figure 11 Overall view of Tubes and Reflector Hange...

Страница 17: ...erlap position and one in the middle of each 10 reflector length Figure 13 shows the installation of the reflector support bracket Figure 13 Reflector Support Bracket Installation Note Reflectors shou...

Страница 18: ...8 x 3 8 long screws not supplied and secure reflector to the reflector bracket at this point by tightening down 8 x 1 screws supplied with reflector brackets Figure 15 The remaining reflector overlap...

Страница 19: ...Series WTH Page 19 LT105 Feb 2019 Install End Cap as shown in Figure 4 and Figure 16 Figure 16 Reflector End Cap Installation...

Страница 20: ...o reduce the above clearance to combustibles distance use miter reflectors see Figure 18 and refer to Clearance to Combustibles information Figure 17 90 Elbow and U Tube Assembly Detail Elbows or U Tu...

Страница 21: ...ds reflectors and or bottom shield as required Refer to Figure 18 and Figure 19 for details Side shields are 124 long Fasten one side shield per reflector with 8 x 3 8 screws Use three side shield bra...

Страница 22: ...eries WTH Page 22 LT105 Feb 2019 BOTTOM SHIELD REFLECTOR INSTALLATION Bottom shields need not overlap Each 5 section is held with two support brackets see Figure 19 Figure 19 Bottom Shield Installatio...

Страница 23: ...nstallation A general ordered sequence for installation is provided below for reference HANGERS INSTALLATION Suspension mechanism must allow for lateral tubing expansion A minimum 12 length welded lin...

Страница 24: ...er on the chain with Quick Links refer to Figure 21 Figure 22 Figure 22 Typical Hanging Points Place the first flanged aluminized tube in the first two hangers Figure 23 Be sure the flange is toward t...

Страница 25: ...n It is required that the first hanging point be 3 to 6 from the burner mounting flange and tube weld seam must face down refer to Figure 23 for more details Figure 23 Installation of First section of...

Страница 26: ...ly and alternately Tightening one band completely before the other may result in an undesirable wrinkle in the liner refer to Figure 25 Be sure not to over torque the coupling Torque coupling to 15 25...

Страница 27: ...hanger The small tab on the baffle is folded over the end of the tube and clamped in place by the vent connector and vent system refer to Figure 27 Note Baffles are always placed at the end of the las...

Страница 28: ...ries WTH Page 28 LT105 Feb 2019 Figure 27 Baffle Installation A general overall view of the tubes and reflector hangers are shown in Figure 28 below Figure 28 Overall view of Tubes and Reflector Hange...

Страница 29: ...erlap position and one in the middle of each 10 reflector length Figure 30 shows the installation of the reflector support bracket Figure 30 Reflector Support Bracket Installation Note Reflectors shou...

Страница 30: ...lap together with a minimum of 2 8 x 3 8 long screws not supplied and secure reflector to the reflector bracket at this point by tightening down 8 x 1 screws supplied with reflector brackets Figure 32...

Страница 31: ...Series WTH Page 31 LT105 Feb 2019 Figure 32 Reflector Supports Installation and Reflector Overlap Install End Cap as shown in Figure 33 Figure 33 Reflector End Cap Installation...

Страница 32: ...thout reflectors To reduce the above clearance to combustibles distance use miter reflectors see Figure 35 and refer to Clearance to Combustibles information Figure 34 90 Elbow and U Tube Assembly Det...

Страница 33: ...Series WTH Page 33 LT105 Feb 2019 MITERED REFLECTOR INSTALLATION If used install the Mitered Reflector as shown below Figure 35 Figure 35 Mitered Reflector Installation...

Страница 34: ...lectors and or bottom shield as required Refer to Figure 36 and Figure 37 for details Side shields are 124 315cm long Fasten one side shield per reflector with 8 x 3 8 screws Use three side shield bra...

Страница 35: ...eries WTH Page 35 LT105 Feb 2019 BOTTOM SHIELD REFLECTOR INSTALLATION Bottom shields need not overlap Each 5 section is held with two support brackets see Figure 37 Figure 37 Bottom Shield Installatio...

Страница 36: ...exhanger only It can be installed either directly to the heater reflector or as part of a T Bar installation where the heater is above the ceiling structure Refer to Figure 38 and Figure 39 below for...

Страница 37: ...tically IMPORTANT Maximum total vent length allowed for any model heater is 30 9m Maximum total fresh air inlet duct length allowed for any model heater is 30 9m Total of vent length plus outside air...

Страница 38: ...imum Figure 40 Horizontal Venting Vertical Venting The heater operates at a negative vent pressure Refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the USA and CSA B149 1 Installation Codes...

Страница 39: ...ers refer to ANSI Z223 1 and CSA B149 1 Use of approved thimble to pass through combustible roof material is required Additionally B type vent materials are required for stacks above the roof line Use...

Страница 40: ...outside air terminal must be of an approved type and should be located at an elevation equal to or below the vent terminal elevation to prevent back venting of flue gases into the burner compartment...

Страница 41: ...n the USA and CSA B149 1 and B149 2 Installation Codes in Canada Before connecting burners to the gas supply system verify that high pressure testing of the system has been completed Failure to do so...

Страница 42: ...n Electric Code CSA C22 1 in Canada and must comply with all local requirements Heaters may also be controlled with a manual line switch or timer switch in place of the thermostat Refer to Figure 30 3...

Страница 43: ...This allows the products of combustion to be removed from the heat exchanger to avoid nuisance condensation and increase heat exchanger life When using a line voltage thermostat and the heat requireme...

Страница 44: ...turbulator flue baffle in the flue end of the heater as mentioned in the manual Is the baffle tab located at 6 o clock and bent as mentioned in the manual 10 Did you install end caps 11 Did you obser...

Страница 45: ...ssure tap in gas supply system Is combination gas control gas valve or the ignition module is faulty Burner Does Not Light Is spark visible through site glass during ignition trial If no further elect...

Страница 46: ...Series WTH Page 46 LT105 Feb 2019 Troubleshooting Chart...

Страница 47: ...G143 HONEYWELL VALVE TRAIN REPLACEMENT KIT LPG 12 CE020 AIR SWITCH MODELS 40 000 60 000 BTU 4 CE058 TRANSFORMER CE021 AIR SWITCH MODELS 80 000 100 000 BTU 5 CE004 BLOWER FOR U T MODELS 40 000 TO 175 0...

Страница 48: ...er any shipping installation or other costs incurred in the repair or replacement of the product No materials will be accepted for return without authorization This warranty will not apply if in the j...