Solar Hybrid Inverter V1.0
26
43
2-section end
charging time
[43] 00:00:00 Default Set Range: 00: 00-23: 59: 00
44
3-section start
charging time
[44] 00:00:00 Default Set Range: 00: 00-23: 59: 00
45
3-section end
charging time
[45] 00:00:00 Default Set Range: 00: 00-23: 59: 00
46
Sectional charging
function
[46] DIS Default
Disable this Function
[46] ENA
After the sectioned charging function is enabled, the
power supply mode will change to BT1ST, and system will
enable the mains power charging only in the set charging
period or battery over discharge; If the sectioned
discharge function is enabled at the same time, the
power supply mode of the system will change to AC1ST,
which only enable the mains charging in the set charging
period, and switch to the battery inverter power supply
mode in the set discharge period or when the mains
power is off
47
1-section start
discharging time
[47] 00:00:00 Default Set Range: 00: 00-23: 59: 00
48
1-section end
discharging time
[48] 00:00:00 Default Set Range: 00: 00-23: 59: 00
49
2-section start
discharging time
[49] 00:00:00 Default Set Range: 00: 00-23: 59: 00
50
2-section end
discharging time
[50] 00:00:00 Default Set Range: 00: 00-23: 59: 00
51
3-section start
discharging time
[51] 00:00:00 Default Set Range: 00: 00-23: 59: 00
52
3-section end
discharging time
[52] 00:00:00 Default Set Range: 00: 00-23: 59: 00
53
Sectional discharge
function
[53] DIS Default
Disable this Function
[53] ENA
After the sectioned discharge function is enabled, the
power supply mode will change to AC1ST and the system
will switch to battery inverter power supply only during
the set discharge period or when the mains power is off
54
Current date setting [54] 00:00:00 Default Set Range: 00:01: 01-99:12:31
55
Current time setting [55] 00:00:00 Default Set Range: 00:00: 00-23:59: 59
56
Leakage protection
function
[56] DIS Default
Disable this Function
[56]ENA
Enable leakage protection function