Mini-VARIO and VARIO Manual Motor Control Switches
Specifications
5
3/99
© 1999 Square D All Rights Reserved
Switch Type
VN12
VZN12
V02
VZ02
VN20
VZN20
V01
VZ01
V0
VZ0
VVD0
VVE0
V1
VZ1
VVD1
VVE1
Electrical Characteristics, DC Operation
Rated Operational Current (contacts in series)
DC-1 (L/R = 1 ms)
24 V
1 contact
A
12
20
25
32
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
48 V
1 contact
A
12
20
25
32
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
60V
1 contact
A
12
20
25
32
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
110 V
1 contact
A
1.5
2
9
10
2 contacts
A
8
10
12
16
3 contacts
A
12
20
25
32
220 V
1 contact
A
1.5
2
2.5
3
2 contacts
A
7
8
10
12
3 contacts
A
10
14
16
20
250V
1 contact
A
0.6
0.7
0.8
1
2 contacts
A
3
4
6
8
3 contacts
A
8
10
12
16
Rated Operational Current (contacts in series)
DC-2 TO DC-5
24 V
1 contact
A
12
20
25
32
(L/R = 1ms)
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
48 V
1 contact
A
12
20
25
32
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
60 V
1 contact
A
10
14
16
20
2 contacts
A
12
20
25
32
3 contacts
A
12
20
25
32
110 V
1 contact
A
1.5
2
2.5
3
2 contacts
A
3
4
5
6
3 contacts
A
12
20
25
32
220 V
1 contact
A
0.4
0.5
0.5
0.8
2 contacts
A
1.4
1.5
1.5
2
3 contacts
A
1
2
3
4
250 V
1 contact
A
0.3
0.4
0.5
0.8
2 contacts
A
0.4
0.6
0.8
1
3 contacts
A
1.2
2.4
1.6
2
Other Characteristics
Mechanical Durability
Millions of Op.
Cycles
0.05
0.1
0.05
0.1
0.1
0.1
Electrical Durability in Cat. AC-21
Millions of Op.
Cycles
0.05
0.1
0.05
0.1
0.1
0.1
Electrical Durability in Cat. DC-1 to 5
Operating
Cycles
30,000
30,000
30,000
30,000
Suitable for Isolation
Yes
Yes
Yes
Yes
Cabling
Flexible Cable + Cable
End
AWG (mm
2
)
12 (4)
10 (6)
12 (4)
10 (6)
10 (6)
10 (6)
Solid Cable
AWG (mm
2
)
12 (4)
8 (10)
12 (4)
8 (10)
8 (10)
8 (10)
Tightening Torque
lb-in (N•m )
6.2 (0.7)
18.6 (2.1)
6.2 (0.7)
18.6 (2.1)
18.6 (2.1)
18.6 (2.1)