5
programming
SCREEN LAYOUT
Red indicates the relay inside the control panel has been energized.
LEVEL IN INCHES–actual water level in the cold water basin
GOTO SETUP–use to program sensor heights and setpoint levels.
Default password is 1492
INFO–use to see programmed levels
Requires field programming
1. Measure and program the distance between sensor and water basin floor
2 Program the water level setpoints
3. Operate WATER MAKE UP selector switch to operate
solenoid valve circuit
The WATER MAKE UP selector switch controls the makeup
solenoid circuit
HAND position–manually energizes remote makeup solenoid
OFF position–no power to remote makeup solenoid
AUTO position–ultrasonic makeup water level sensor activated
Note
➠