4–Check Geareducer oil for sludge or water by draining off and testing a 

sample as outlined in the Geareducer User Manual

.

 Check Geareducer oil 

level at “oil level” mark on the side of the case. Add oil as required. The oil 
level placard must be adjusted so that its “full” mark is at the same eleva-
tion as the “full” mark on the side of the Geareducer case. Check oil lines 
to be sure there are no leaks. Refer to the Geareducer User Manual for oil 
filling procedure and list of recommended lubricants.

5–Rotate fan by hand to be sure of free rotation and ample tip clearance. 

Refer to the Fan User Manual

.

6–Check motor insulation with a megohm meter. Refer to the Maintenance 

Section of Marley “

Fan Motor”

 User Manual

.

7–Lubricate the motor according to motor manufacturer’s instructions.
8–Test run each fan separately for a short time. Check for excessive vibration 

or unusual noise. If either is present, see 

Troubleshooting Guide

 on pages 

14 and 15 of this manual. Fan must rotate clockwise when viewed from 
above. Recheck Geareducer oil level.

9–Check functioning of make-up water supply. Make sure the blowdown will 

carry the proper amount of water.

Starting Procedure

WATER SYSTEM–Fill the cold water collection basin and circulating water 
system until the operating water level is reached. Prime and start the circulat-
ing water pumps. Increase the flow of circulating water gradually to design 
water flow rate to avoid water hammer which could damage the distribution 
piping system.

Clean the sump screens several times during the first weeks of 
operation. After this, clean sump screens weekly.

When starting in cold weather, follow procedures outlined in Cold 
Weather Operation.

STARTING FAN–Operate the fan for 30 minutes to permit the Geareducer 
oil to come up to operating temperature and check the motor load with watt 
meter, or take operating volt and ampere readings and calculate motor hp. 
Refer to the Fan User Manual for instructions. Pitch fans if required to pull 
correct contract horsepower when circulating design water rate at design 
hot water temperature.

Note

Note

operation

Содержание Marley F400

Страница 1: ...F400 counterflow cooling tower OPERATION MAINTENANCE Z0248630_D ISSUED 8 2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Страница 2: ...els or to important information concerning the life of the product Indicates presence of a hazard which can cause severe personal injury death or substantial property damage if ignored Indicates prese...

Страница 3: ...188 and Guideline 12 2 Do NOT attempt any service unless the fan motor is locked out 3 Remove any sediment from the cold water collection basin sump and screens Use a water hose to flush cold water c...

Страница 4: ...15 of this manual Fan must rotate clockwise when viewed from above Recheck Geareducer oil level 9 Check functioning of make up water supply Make sure the blowdown will carry the proper amount of water...

Страница 5: ...approximate the contract requirements and the nozzle pressure should be kept constant Lower pressures may indicate excessive losses in the piping system and or insufficient pump capacity greater press...

Страница 6: ...everse air flow by aspiration and may cause water blowout and therefore must be done with caution and moni toring For automatic operation a timer switch can be provided to shut the fan down for a few...

Страница 7: ...piping and nozzles clean and free of dirt algae and scale Algae and scale may clog nozzles eliminators fill and piping and may collect on the equipment served thus reducing its performance An access...

Страница 8: ...m the circulating system Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale The amount of blowdown required depends upon the cooling range the...

Страница 9: ...wer or heat exchangers Their presence can interfere with cooling efficiencies Proprietary compounds are available from water treating companies for the control of slime and or algae however compounds...

Страница 10: ...ot form scale in the cooling tower if carbonate scaling does not occur in the condenser Exceptions If make up water contains surplus free carbon dioxide scaling may be inhibited in the condenser but m...

Страница 11: ...before attempting repairs Apply protective coating as required to all metal parts Particular attention should be given to mechanical equipment supports drive shaft and drive shaft guards Mechanical E...

Страница 12: ...rer s instructions Motors with sealed bearings do not require lubrication maintenance 2 Each month run motor until it has reached operating temperature Space heaters are recommended If space heaters a...

Страница 13: ...larly in accordance with ASHRAE Standard 188 and Guideline 12 Workers performing decontamination procedures must wear personal protective equipment PPE as directed by their facility safety officer Coo...

Страница 14: ...ket fits or bearing Rotor unbalance Rebalance Cooling fan hitting end bell guard Reinstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three line...

Страница 15: ...Have motor service person check motor Wrong motor rotation Wrong sequence of phases Switch any two of the three motor leads Geareducer noise Geareducer bearings If new see if noise disappears after on...

Страница 16: ...tion 1 Good 2 Keep an eye on it 3 Needs immediate attention 1 2 3 Comments Structure Casing Material Structural Material Fan Deck Material Stairway Material Ladder Material Handrails Material Interior...

Страница 17: ...Material Fans Manufacturer Fixed Pitch Adjustable Pitch Diameter Number of Blades Blade Material Hub Material Hub Cover Material Blade Assembly Hardware Tip Clearance min max Vibration Level Fan Cylin...

Страница 18: ...M 9 Check oil for water and sludge M 10 Change oil S 11 Check fan blade tip clearance S 12 Check water level D D 13 Check for leakage W S S S 14 Inspect general condition S S S S Y S Y S Y S S S Y S...

Страница 19: ......

Страница 20: ...ERVED In the interest of technological progress all products are subject to design and or material change without notice F400 cooling tower US E R MAN UAL SPX COOLING TECHNOLOGIES INC 7401 WEST 129 ST...

Отзывы: