SPX Hankison HPRP 1000 Скачать руководство пользователя страница 6

6

3.  Setting Schedule

a.  Use the ‘Up’ and ‘Down’ arrow buttons to select desired 

“Day of week + on/off ”.  Press ‘Enter’ to accept new 

value

b.  Use the ‘Up’ and ‘Down’ arrow buttons to set hour (00 

to 23).  Press ‘Enter’ to accept new value

  Note:  If the hour setting is ‘IGNORE’, Press ‘Enter’ 

again to move the cursor under the “Day of week + 

on/off”.

c.  Use the ‘Up’ and ‘Down’ arrow buttons to set minutes 

(00, 10, 20, 30, 40, 50; not shown if hour setting is 

‘IGNORE’).  Press ‘Enter’ to accept new value and 

return to “Day of week + on/off ”.  Repeat steps a 

through c as needed. 

d.  Push ‘ESC’ at any time to return to the Main Menu.

4.  Hours To Service

a.  Use the ‘Up’ and ‘Down’ arrow buttons to scroll through 

the range of permissible values (0 to 8760) before 

service reminder is initiated.  Press ‘Enter’ to accept 

new value. (Only hours that refrigeration compressor is 

operating are counted).

b.  Press ‘ESC’ at any time to return to the Main Menu.

NOTE: On dryers with air-cooled condensers, regular 

condenser cleaning is recommended. Dirtiness of 

ambient air at installation site will determine frequency 

of  service.  Typically once a month is recommended.
NOTE: All dryers contain an integral 3 micron filter.  

As the filter element accumulates solid contaminants, 

differential pressure increases.  Solid particulate load in 

the compressed air supply will determine frequency of 

service.  Typically element changeout is recommended 

at least annually. 

5.  Alarm History

a.  Use the ‘Up’ and ‘Down’ arrow buttons to scroll through 

the last twenty (20) alarms beginning with the most 

recent alarm.  
NOTE: The number at the end of the top line with a 

cursor underneath identifies which of the past twenty 

alarms is being displayed.

b.  Press ‘ESC’ at any time to return to the Main Menu.
c.  To clear the alarm history, press and hold the ‘Enter’ 

button then press the ‘Up’ arrow button.  Release both 

buttons.

6.  Push ESC button to exit program mode.
 

NOTE: If after 60 seconds no button is pressed while 

in Program Mode, the audible alarm sounds for five (5) 

seconds and the controller exits program mode.  Dryer will 

resume previous operating mode.

C.  Starting Dryer
IMPORTANT: Dryer must be energized 24 hours before starting 

refrigeration compressor.
NOTE: It is recommended that dryer be started 15 minutes 

before compressed air flow begins.
1.  On water-cooled models: after 24 hours and before 

starting dryer, begin cooling water flow.

2.  Check for proper electrical voltage.

3.  Slowly pressurize unit air side by opening inlet isolation 

valve. Check for leaks.

4.  After 15 minutes, open outlet isolation valve slowly.
5.  Close air bypass valve.
6.  Dryer may be operated in Manual or scheduled modes.
NOTE: Check for correct phasing of unit. On air-cooled 

models: check fan rotation (air must be pulled through the 

condenser). Fans may not start immediately or may cycle on 

and off. If rotation is in the wrong direction follow the procedure 

below. On water-cooled models: After starting dryer if an 

unusual noise is heard and the discharge line does not get 

hot, stop the dryer, reverse two power leads, restart, and verify 

discharge line gets hot.

a.  Manual mode - push ‘On/Off ’ button - refrigeration 

compressor will start and run, green Compressor-on 

light will illuminate. In this mode compressor will run 

continuously and will not be turned on and off by the 

monitor. MANUAL OVERRIDE will appear on interface 

panel.

b.  Schedule mode - push ‘Schedule On/Off and Enter’ 

button.  SCHEDULE RUNNING will appear on the 

interface panel. The refrigeration compressor will 

continue to be on or off (as selected in the Manual 

Override Mode) until the next scheduled event. The 

compressor will then turn on or off as programmed.

NOTE: Dryer may be returned to the manual mode at any 

time using the ‘Schedule On/Off and Enter’ button. MANUAL 

OVERRIDE will appear on interface panel. To reinstitute 

Schedule, push the ‘Schedule On/Off and Enter’ button again.
NOTE: Restart after the power interruption. Unit will be in 

MANUAL OVERRIDE mode, refrigeration compressor, off 

when power is restored after power interruption.
7.  To reinstitute SCHEDULE RUNNING: push ‘Schedule On/

Off and Enter’ button.

IMPORTANT: Dryer must be energized 24 hours before 

refrigeration compressor is started.

D.  Operating Check Points
1.  Check that green Power-on light is illuminated.
2.  Check that green Compressor-on light is illuminated if 

dryer is on in the manual mode or it is a scheduled on 

time. 

IMPORTANT:  Refrigeration compressor must be restarted 

after power interruption.
3.  Check Interface Panel.
NOTE: Interface panel will scroll through three screens 

(Current Time/Operating Status, Hours to Service, and Total 

Operating Hours).

a.  Verify that current time is correct.
b.  Check HRS TO SERVICE: this indicates time 

remaining until service is required; allow time for 

required maintenance items to be ordered.

c.  Check operating status:
  MANUAL OVERRIDE - Dryer is either running 

continuously (not being controlled by the scheduled 

on/off times) or the refrigeration compressor has been 

shut off using the ‘On/Off’ button. 

Содержание Hankison HPRP 1000

Страница 1: ...11 ELECTRICAL SCHEMATICS Models 1000 and 1250 12 13 Model 1500 14 15 Models 1750 2000 and 2500 16 17 Model 3000 18 19 DIMENSIONS WEIGHTS 20 ENGINEERING DATA 21 22 TROUBLESHOOTING GUIDE 23 PARTS LIST...

Страница 2: ...weather Damage to electrical and control components may result IMPORTANT WATER COOLED UNITS If unit is shut down below freezing temperatures the water cooled condenser may freeze and cause permanent...

Страница 3: ...r E Standard units are designed to operate in ambients Air cooled 40 to 110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C F Dryer is designed to operate at all altitudes no adjustment for altitude is...

Страница 4: ...EDD discharges condensate removed by the separator B All dryer models are supplied with one EDD Models with the additional optional oil removal filter are supplied with a second EDD C The drains are...

Страница 5: ...nting 2000 to 2099 Press Enter to accept new value d Use the Up and Down arrow buttons to set month three letter abbreviation Press Enter to accept new value e Use the Up and Down arrow buttons to set...

Страница 6: ...age 3 Slowly pressurize unit air side by opening inlet isolation valve Check for leaks 4 After 15 minutes open outlet isolation valve slowly 5 Close air bypass valve 6 Dryer may be operated in Manual...

Страница 7: ...ay will be illuminated DRAIN electric drain contains a high water level alarm that activates if drain fails to discharge f Check drain operation push Drain push to test button to energize electric dra...

Страница 8: ...1 Unit of measure selection pressure pounds per square inch 2 Unit of measure selection pressure kilograms per square centimeter 3 Unit of measure selection pressure bar 4 Indicates that predicted num...

Страница 9: ...intelligence calculated optimum time b Need for battery replacement Battery Icon and red LED will flash 2 5 Filter Monitor Power Supply Each Filter Monitor receives transformed DC power from the contr...

Страница 10: ...in the operational limits Ref 3 2 C 2 e through h 3 2 Annual Maintenance A Check all terminals in the switchgear cabinet and tighten them up if necessary Check to be sure the unit is de energized B Ma...

Страница 11: ...using Caution is necessary as the system may still be under slight residual pressure g Remove all screws except one and swing flange 3 to the side h Pull out the old cartridges 4 i Push new cartridges...

Страница 12: ...3 TB1 PE TB1 19 L2 L1 K43 F13 M L1 3 L2 3 L3 3 L1 3A L2 3A L3 3A FAN 1 25 KW 460 VAC 1 95 RLA TB1 7 TB1 9 TB1 11 TB1 PE HEATER 27 W 460VAC 0 06A K62 1A 1A 1A F22A F22B F22C L1 5 L3 5 L1 5 L2 5 40A ELE...

Страница 13: ...W4 RED BLK B61 10 11 25 25 EVAPORATOR TEMP SENSOR K62 COMPRESSOR CONTACTOR SHT 1 16G 48D SHT 2 38C 40D COMPRESSOR ENERGIZED HEATER ENERGIZED DRAIN 1 ALARM DRAIN 2 ALARM REFRIGERANT HIGH PRESSURE REFRI...

Страница 14: ...L2 3A L3 3A FAN 1 1 05 KW 460 VAC 1 8 RLA TB1 7 TB1 9 TB1 11 TB1 PE HEATER 27 W 460VAC 0 06A K62 1A 1A 1A F22A F22B F22C L1 5 L3 5 L1 5 L2 5 40A ELECTRICAL SUPPLY 480VAC 60Hz 3 PH GND TB1 PE F22 MOUNT...

Страница 15: ...6 W9 K62 19 TB2 7 26 W11 9 TB2 9 26 S67 W3 GND W5 W4 RED BLK B61 10 11 25 25 EVAPORATOR TEMP SENSOR K62 COMPRESSOR CONTACTOR SHT 1 16G 52D SHT 2 40C 42D COMPRESSOR ENERGIZED HEATER ENERGIZED DRAIN 1 A...

Страница 16: ...3 M L1 3 L2 3 L3 3 L1 3A L2 3A L3 3A FAN 1 1 05 KW 460 VAC 1 8 RLA TB1 7 TB1 9 TB1 11 TB1 PE HEATER 27 W 460 VAC 0 06A K62 1A F22A F22B F22C TB1 PE FU22 1 TB2 1 T22 240 277 400 480 575 VAC PRIMARY 24...

Страница 17: ...7 26 W11 9 TB2 9 26 S67 W3 GND W5 W4 RED BLK B61 10 11 25 25 REFRIGERANT HI PRES EVAPORATOR TEMP SENSOR K62 COMPRESSOR CONTACTOR SHT 1 14G 48D SHT 2 40C 40D COMPRESSOR ENERGIZED HEATER ENERGIZED DRAIN...

Страница 18: ...L2 3A L3 3A FAN 1 1 05 KW 460 VAC 1 8 RLA TB1 7 TB1 9 TB1 11 TB1 PE HEATER 27 W 460 VAC 0 06A K62 1A 1A 1A F22A F22B F22C FU22 1 TB2 1 T22 240 277 400 480 575 VAC PRIMARY 24 120 VAC SECONDARY 100VA L1...

Страница 19: ...EFRIGERANT HIGH PRESSURE REFRIGERANT LOW PRESSURE REMOTE START STOP LOCAL REMOTE SELECTION DRAINTEST PHASE CHECK ALARM A COMPRESSOR STOP EMM II SHT 1 60J SHT 1 58J 24VAC TB2 2 ALARM B MONITORING TB2 2...

Страница 20: ...40 3 4 1035 50 3 4 1289 50 3 4 1289 12 1 2 318 13 1 4 337 13 1 4 337 12 7 8 327 11 1 4 286 11 1 4 286 8 3 4 222 8 1 2 216 8 1 2 216 1146 520 1521 690 1547 702 3 ANSI Flg 4 ANSI Flg 4 ANSI Flg 1750 200...

Страница 21: ...acity Rated Flow BTU hr 60 Hz a c 42 300 52 700 65 700 78 400 78 400 98 800 125 700 50 Hz a c 46 500 58 100 73 400 87 600 87 600 112 900 140 200 Refrigerant Type R 404A Refrigerant Charge See Data Tag...

Страница 22: ...1 1 90 1 85 1 85 1 57 1 10 Nominal Voltage 575 3 60 Voltage Range 518 633 Input Power Rated Flow watts 6 130 7 290 9 470 11 360 11 360 15 030 19 670 Minimum Circuit Ampacity 10 12 16 19 19 22 31 Maxim...

Страница 23: ...clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch 2 Water cooled Cooling temperature too high flow too low clogged strainer faulty water regulating valve...

Страница 24: ...Air Temperature 3210927 3210927 3210927 3210927 3210927 3210927 3210927 Strainer Hot Gas Bypass Line 4006435 4006435 4006435 4006436 4006436 4006436 4006436 Switch Fan Cut out 1 3230765 3230765 323076...

Страница 25: ...25 NOTES...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...ING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITYAND THE IMPLIED WARRANTY OF FITNESS F...

Отзывы: