Marley
/
Sigma F Series
Cooling Tower
/
Engineering Data : Piping Plan 2
7
C
MOTOR
C
F
COLUMN AND
ANCHOR BOLT
TYP. SINGLE CELL
D
TYP. MULTICELL
CL
COLUMN AND
ANCHOR BOLT
CL
INLET
C L
TOWER
AND FAN
C L
FAN
CL
FAN
CL
INLET
CL
INLET
CL
F
FAN TOWER
CL
INLET
CL
MOTOR
CONCRETE
BASIN OPTION
B
DIAMETER
CROSSOVER PIPE
STAINLESS
STEEL BASIN
OPTION
E
FACE OF
A
DIA. GALVANIZED FLANGE
PIPING
LOADS SUPPORTED
BY OTHERS
PIPING
LOADS SUPPORTED
BY TOWER
FLANGE IS
3
/
4
"
THICK. BOLT
CIRCLE CONFORMS TO 125 LB.
ANSI SPECIFICATIONS
BASE OF
TOWER COLUMNS
NOTE
1
Use this bulletin for preliminary layouts only.
Obtain current
drawings from your Marley representative.
2 Pumping head contributed by the tower is static lift E. Actual
pumping head will vary according to tower circulating GPM.
Total pumping head will be furnished at time of proposal.
3 If your application requires a bypass system, recommended
location is through the tower endwall into the plenum area.
Review of the system by SPX engineering is required.
4 All header and riser piping to be furnished by others.
A corrosion-resistant material or coating for piping is
recommended. All inlet piping loads, including thrust and
seismic, outside of tower plan area must be supported by
others.
Tower
Model
Flow/Cell
GPM
Dimensions
A
B
C
D
E
F
F1210
1050-5750
12"
10"
8'-0"
16'-0"
15'-10
7
⁄
8
"
7'-6"
F1220
1050-5750
14"
12"
8'-0"
16'-0"
15'-11
7
⁄
8
"
8'-6"
F1230
1320-7200
14"
12"
10'-0"
20'-0"
15'-11
7
⁄
8
"
8'-6"
F1240
1500-8650
14"
12"
12'-0"
24'-0"
15'-11
7
⁄
8
"
8'-6"
F1250
1500-8650
16"
14"
12'-0"
24'-0"
16'-0
7
⁄
8
"
10'-6"
F1260
1850-10100
16"
14"
14'-0"
28'-0"
16'-0
7
⁄
8
"
10'-6"
PLAN
END ELEVATION