FILL:

  Heat transfer fill media shall be crosscorrugated 

20 mil PVC sheets supported by stainless steel tubes 

which, in turn, are suspended by stainless steel tension 

hangers from concrete support beam members.

DRIFT  ELIMINATORS:

    Drift  eliminators  shall  be 

supplied in a 3 pass cellular arrangement of bonded 

17 mil PVC sheets. Drift loss shall not exceed ______% 

of circulating water.

HOT  WATER  DISTRIBUTION  SYSTEM:

  Hot  water 

distribution system in each cell shall be supplied with 

a single interior inlet terminating 1'-0 below bottom of 

the tower filling. Materials will be of inert PVC and RTR 

and polypropylene piping supported by the support 

beams utilized to carry heat transfer fill media.

FAN CYLINDERS:

  Fan cylinders shall have eased inlet 

design and be of molded fiber reinforced polyester 

with a minimum height of 6' 0.

OPTlONS:

    Factory  Mutual  Approval.  The  tower 

shall  include  all  design  and  material  modifications 

necessary  to  meet  the  fire  rating  requirements  of 

Factory Mutual. The product proposed shall be listed 

in the FM Approval Guide, latest edition.
Masonry structure options at owner’s election:
1-Shell  structure  design  shall  be  by  cooling  tower 

manufacturer.
2-Shell structure and cold water basin design shall be 

by cooling tower manufacturer.
3-Shell  structure  and  cold  water  basin  design  shall 

be  by  cooling  tower  manufacturer.  Shell  structure 

construction including materials and labor shall be 

by cooling tower manufacturer.
4-Shell structure and cold water basin design shall be 

by  cooling  tower  manufacturer.  Shell  structure  and 

cold water basin construction including materials and 

labor shall be by cooling tower manufacturer.

WARRANTY:

  Warranty  on  all  components  against 

defective  materials  and  workmanship  will  be 

extended for a period of one (1) year following initial 

operation  but  not  exceeding  eighteen  (18)  months 

from  date  of  shipment.  Components  that  may  fail 

within  warranty  period  shall  be  repaired  and/or 

replaced including freight and installation labor.
Thermal  testing  of  cooling  tower  will  be  done 

within  one  (1)  year  following  structural  completion 

in  accordance  with  Cooling  Technology  Institute 

Acceptance Test Code CTI ATC 105. In the event test 

results indicate deficiency, manufacturer shall make 

alterations to overcome indicated deficiency and if 

such alterations are inadequate manufacturer shall 

refund a percentage of contract price proportional to 

tower deficiency.

SPECIFICATIONS

COOLING  TOWER:

    Furnish  and  install  (1)  Induced 

Draft  Counterflow  Cooling  Tower.  Cooling  tower 

shall  be______ft.  long  x  ______ft.  wide  x  ______  ft. 

overall  height  with  a  maximum  operating  weight 

of______lbs.  Cooling  tower  shall  consist  of_____fan 

cells  with  a  maximum  of_____total  fan  horsepower 

and a maximum pump head of______ft.
Other  contractor(s)  will  furnish  all  external  piping, 

valves,  pumps,  electrical  equipment  other  than 

cooling tower fan motors, wiring, controls, etc. all in 

accordance  with  general  overall  dimensions  to  be 

supplied by cooling tower manufacturer. All internal 

components of cooling tower as described following 

will be furnished and installed by the cooling tower 

manufacturer.

CAPACITY:

    Cooling  tower  shall  be  selected  and 

guaranteed  to  cool______GPM  of  water  from 

______°F  to  ______°F  at  ______°F  entering  wet  bulb 

temperature.

MECHANICAL EQUIPMENT:

  Mechanical equipment 

shall be designed specifically for cooling tower usage 

and shall be mounted on a rigid unitized HDG steel 

support  to  assure  permanent  drivetrain  alignment. 

Cooling tower manufacturer shall be responsible for 

equipment warranty.

FANS:

    Fans  shall  be  of  a  multi-blade  propeller 

type and blades shall be constructed of solid glass 

reinforced polyester, cast aluminum alloy or hollow 

glass reinforced epoxy. Hubs shall be HDG steel cast 

iron or aluminum plate. Blades shall be individually 

adjustable for required pitch angles.

DRIVESHAFTS:

  Driveshaft tubes and flanges shall be 

manufactured of type 304 stainless steel. Couplings 

shall  be  hot  dip  galvanized  cast  iron,  joined  to 

the  driveshaft  by  flexible  neoprene  bushings  and 

cadmium plated steel inserts. Connecting hardware 

shall be 300 stainless steel. Driveshaft assemblies shall 

be dynamically balanced at the factory at full motor 

speed.

SPEED REDUCERS:

 Speed reducers shall be provided 

for  right  angle  fan  drive  and  shall  be  designed  to 

AGMA  standards  for  continuous  duty  operation, 

capable of reverse operation. Oil fill and drain lines 

are to be extended outside the fan cylinder to an oil 

level sight glass.

ELECTRIC MOTORS:

  Electric motors shall be_______ 

speed,  single  winding,  variable  torque,  _____  hp 

maximum, TEFC, and specially insulated for cooling 

tower duty. Speed and electrical characteristics shall 

be _____ RPM, _____ phase, _____ hertz, _____ volts. 

If the load applied to the motor exceeds 90% of the 

nameplate rating, then the motor shall have a 1.15 

service factor and the service factor beyond 1.0 shall 

not be considered available for load. 

Содержание CoolingTower Marley MS

Страница 1: ...Marley MS CoolingTower...

Страница 2: ...design and manufacture cooling towers of virtually any capacity and configuration More than 400 Marley tower models are available to service the application requirements of air conditioning industrial...

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...mance and clog resistant designs are both available for a wide range of thermal and water quality requirements ELIMINATORS Marley XCEL drift eliminator panels formed from PVC sheets into a cellular co...

Страница 9: ...afts are built from stainless steel or carbon fiber composite tubes with stainless steel flanges All Marley driveshafts are dynamically balanced at the factory to minimize operating vibrations GEAREDU...

Страница 10: ...e you from the expense and nuisance of cleaning clogged nozzles FAN CYLINDERS Marley FRP fan cylinders feature venturi shaped eased inlets and close fan tip clearance for maximum efficiency If require...

Страница 11: ...e of contract price proportional to tower deficiency SPECIFICATIONS COOLING TOWER Furnish and install 1 Induced Draft Counterflow Cooling Tower Cooling tower shall be______ft long x ______ft wide x __...

Страница 12: ...AS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Coolin...

Отзывы: