SPT WA-S7000E Скачать руководство пользователя страница 10

Safety 

Precautions

 Page 10

 

 

 

 

 

    cylinders. (No more than 80 % volume liquid charge).     i)  Do not exceed the maximum working 

    pressure of thecylinder, even temporarily.     j)  When the cylinders have been filled correctly and the 

    process completed, make sure that the cylinders and the equipment are removed from site promptly 

    and all isolation valves on the equipment are closed off.     k) Recovered refrigerant shall not be charged 

    into another refrigeration  system unless it has been cleaned and checked.

15.Labelling

    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The 

    label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment 

    contains flammable refrigerant.

16.Recovery

    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended 

    good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, 

    ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct 

    number of cylinders for holding the total system charge is available. All cylinders to be used are 

    designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the 

    recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 

    valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before 

Before carrying out this procedure, it is essential that the technician is completely familiar with the 

equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before 

the task is commenced. 

14.Decommissioning

a) Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before 

attempting the procedure ensure that: Mechanical handling equipment is available, if required, for 

handling refrigerant cylinders;All personal protective equipment is available and being used correctly; 

The recovery process is supervised at all times by a competent person; Recovery equipment and 

cylinders conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a 

vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the

system.     f) Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the 

recovery machine and operate in accordance with manufacturer's instructions.    h) Do not overfill 

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure

that contamination of different refrigerants does not occur when using charging equipment. Hoses or 

lines shall be as short as possible to minimise the amount of refrigerant contained in them. 

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 

with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 

finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 

work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 

place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 

ventilation available.

Содержание WA-S7000E

Страница 1: ...on Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference PORTABLE AIR CONDITIONER WA S7000E...

Страница 2: ...ation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Choosing The Right Location Tools Needed Accessories Window Installation Kit Instal...

Страница 3: ...is grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your un...

Страница 4: ...ould be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the su...

Страница 5: ...capes endangers your health when hazar do us substances leak into the ground water and find their way into the food chain Do not use hazardous chemicals to clean or come into contact with the unit Do...

Страница 6: ...reil au gaz en marche ou radiateur lectrique en marche Ne pas percer ni bruler Attention les frigorig nes peuvent tre inodores Please follow the instruction carefully to handle install clear service t...

Страница 7: ...side the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 3 General work area A...

Страница 8: ...uit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be cor...

Страница 9: ...e following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may...

Страница 10: ...Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment i...

Страница 11: ...ted weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in...

Страница 12: ...The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts Diameter 5 9inch Length 59inch Diameter 5 12inch Length 59inch The Energy rating and noise information for unit with 3...

Страница 13: ...square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amount of heat...

Страница 14: ...Hose Drain Hose 1 pc Window Slider Adaptor O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 set 1 pc Window Slider B Remote Controller and Battery on...

Страница 15: ...ders once they are adjusted to the Proper length Window slider A Window slider B Bolt Window slider A Window slider B Window slider C Bolts Step Two Install the Exhaust hose assembly to the unit MODEL...

Страница 16: ...sash and frame as shown Foam seal B Adhesive type shorter Foam seal A Adhesive type Or Or Window slider A Window slider B if required Foam seal C Non adhesive type 3 Cut the non adhesive foam seal C...

Страница 17: ...actual shape shall prevail NOTE Cover the hole using the adaptor cap when not in use max 120cm or 47 inch min 30cm or 12 inch Expansion anchor position Adaptor cap Wall Exhaust Adaptor B Or 5 Insert t...

Страница 18: ...error select models only E4 Display panel communication error EC Refrigerant leakage detection malfunction select models only Shows protection code P1 Bottom tray is full Connect the drain hose and d...

Страница 19: ...nd UP buttons at the same time for 3 seconds to turn off Wireless function and the LED DISPLAY shows OF for 3 seconds press MODE button and UP to turn on Wireless function and the LED DISPLAY shows On...

Страница 20: ...sure the hose is secure so there are no leaks Direct the hose toward the drain making sure that there are no kinks that will stop the warter flowing Place the end of the hose into the drain andmake su...

Страница 21: ...e unit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the app...

Страница 22: ...urn off the unit and clean the filter according to instructions Call a service technician to inspect the unit and top off refrigerant Decrease the set temperature Make sure all windows and doors are c...

Страница 23: ...TANT NOTE REMOTE CONTROLLER Thank you for purchasing our air conditioner Please read this manual carefully before operating your new air conditioning unit Make sure to save this manual for future refe...

Страница 24: ...d Functions sections of this manual for a detailed description of how to use your air conditioner SPECIAL NOTE Button designs on your unit may differ slightly from the example shown If the indoor unit...

Страница 25: ...FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may...

Страница 26: ...SPEED Selects fan speeds in the following order AUTO LOW HIGH TEMP Decreases temperate in 1 F increments Min temperature is 62 F TIMER ON Sets timer to turn unit on see How to Use Basic Functions for...

Страница 27: ...Displayed when remote controller is ON Low speed NO display Medium speed some units High speed Auto fan speed Displayed when TIMER ON time is set Displayed when TIMER OFF time is set Indicated all th...

Страница 28: ...OFF Select DRY mode Set your desired temperature Turn on the air conditioner FAN Mode MODE ON OFF Select FAN mode Turn on the air conditioner Select COOL HEAT mode Set the temperature Turn on the air...

Страница 29: ...2 Cancel either function by setting its timer to 0 0h Point remote to unit and wait 1sec the TIMER ON will be activated Press TIMER OFF button to initiate the OFF time sequence Point remote to unit a...

Страница 30: ...is used to decrease energy use while you sleep and don t need the same temperature settings to stay comfortable This function can only be activated via remote control The sleep function is not availab...

Страница 31: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details CR2712 RG51F H 1...

Страница 32: ...t parts will be new or reconditioned Parts which are replaced become the property of Sunpentown The warranty applies for the use of the product in the USA only What is NOT COVERED Warranty does not in...

Отзывы: