DN-Rev-LOW Maintenance and Operating
Manual
7
MEASURING THE EXHAUST AIRFLOW
The exhaust air is measured along the inlet slot of the ventilator. To ensure accurate results take a reading every foot
along the length of the ventilator is recommended.
VANAXIAL VELOMETER
Hold the
instrument
perpendicular to
the VORTEX
BAFFLE and
parallel to the
throat (inlet slot) of
the ventilator.
Velometer should
not exceed three
inches in
diameter.
Measuring Exhaust Air
Figure
8
PITOT TUBE OR ANEMOM
ETER
Hold the instrument
perpendicular to
the VORTEX
BAFFLE and
parallel to the
throat (inlet slot) of
the ventilator. Take
three readings
across the throat
and average the
results.
Measuring Exhaust Air
Figure 9
Calculating the Exhaust Air
Calculate the average velocity across the inlet slot and refer to the chart below for the
corresponding CFM/ft (l/s/m).
Ventilator Type
Velocity
Exhaust Air Volume
Fpm
m/s
CFM/ft
l/s/m
DN-B-F/DN-DI 450
2.3
100
140
DN-B-F/DN-DI 675
3.4
150
210
DN-B-F/DN-DI 900
4.6
200
275
DN-B-F/DN-DI 1125
5.7
250
340
DN-B-F/DN-DI 1350
6.9
300
410
DN-B-F/DN-DI 1575
8.0
350
480
DN-B-F/DN-DI 1800
9.2
400
550
DN-B-F/DN-DI 2000
10.2
450
620
DN-B-F/DN-DI 2250
11.5
500
690
DN-B-F/DN-DI 2450
12.5
550
755
Chart 1
HANDLE IS UP AND OUT
CORRECT
UP SIDE DOWN
REMOVEABLE INSERT INSTALLATION