Sporlan 10G711B Скачать руководство пользователя страница 2

Page 

 / Bulletin 30-21

OPERATION

“B” TYPE

NORMAL (OUTDOOR) CONDENSER - De-en­er­gized 

See Figure 1. With the pilot valve de-energized, high side pressure 

is prevented from entering the cavity above the piston assembly. 

At the same time, the upper pilot port is open to suction pressure. 

The  resulting  pressure  differential  across  the  piston  moves  the 

piston-seat  assembly  to  close  the  reclaim  condenser  port  (upper 

main port). In this mode, the refrigerant flows to the normal con-

denser. The pilot valve opens the cavity above the piston to suc-

tion. This allows the reclaim condenser to be pumped out through 

a small bleed hole in the piston. The pump out process reduces the 

reclaim  condenser  to  suction  pressure.  Once  suction  pressure  is 

reached, the flow through the bleed hole in the piston stops. There 

is no high to low side bleed with continued operation in the nor-

mal condenser mode. For a more efficient pump out of the reclaim 

condenser,  a  normally  open  solenoid  valve  can  be  added  to  the 

lowest physical location of the reclaim coil to remove liquid.

“C” TYPE

NORMAL (OUTDOOR) CONDENSER - De-en­er­gized 

With the pilot valve de-energized, high side pressure is prevented 

from entering cavity above the piston-seat assembly. At the same 

time the upper pilot port is opened to suction pressure. The result-

ing  pressure  differential  across  the  piston  moves  the  piston-seat 

assembly to close the reclaim (upper) main port, thereby eliminat-

ing high to low side bleed and the resulting capacity loss with the 

system in the normal condenser mode. 

“B” AND “C” TYPE

RECLAIM (REHEAT) CONDENSER - En­er­gized

When the pilot valve is energized, high side pressure is permitted 

to  flow  through  the  lower  pilot  port  at  the  same  time  the  upper 

pilot port is closed to suction. High side pressure build up on top 

of the piston moves the piston-seat assembly to close the normal 

condenser port and open the reclaim (upper) main port. With the 

upper  pilot  port  closed,  there  is  no  high  to  low  side  bleed  and 

resulting capacity loss with the system in the reclaim mode.

Valves using the MKC-1 coil may be used on fluids or gases where 

the temperature does not exceed 240°F, while the valve ambient is 

120°F. The coil is Underwriters Laboratory Class F rated.

TYPES B5D, 8D, 12D & 16D 3-WAY HEAT RECLAIM VALVES

Bulletin 30-21, April 2007 supersedes Bulletin 30-21, June 2001 and all prior publications. © 2007 by Sporlan Division, Parker Hannifin Corporation

Type

Por­t

Size

Con­n­ection­ 

ODF Solder­

Inches

A

B

C

D

E

F

G

H

J

B5D5B

B5D5C

5/8

5/8

5.00 4.36 3.22 3.22 0.79 3.84 0.50 2.94

1.64

8D7B

8D7C

3/4

7/8

5.18

5.06

3.44 3.44 1.13 2.63

0.75

2.89

8D9B

8D9C

1-1/8

5.13

0.91

12D11B

12D11C

1-1/4

1-3/8

6.87 6.94 4.19 4.19 2.38 4.25

0.97

12D13B

12D13C

1-5/8

1.09

12D17B

2-1/8

1.25

16D17B

16D17C

2

2-1/8

8.18 9.53 5.47 5.47 3.50 5.44 1.25 3.17

NOT FOR USE WITH HAZARDOUS OR CORROSIVE FLUIDS

INSTALLATION

PIPING SUGGESTIONS

Valves must be installed in a horizontal or vertical position with 

the coil level with or above the valve body. Install Heat Reclaim 

Valves  so  the  connections  are  in  the  proper  flow  direction  as 

shown in Figure 2.

Figure 3, page 4, shows piping schematics only to illustrate the 

general installation of the Heat Reclaim Valves. Sporlan recom-

mends  that  recognized  piping  references  be  consulted  for  assis-

tance in piping procedures. Sporlan is not responsible for system 

design, any damage resulting from system design, or for misap-

plication of its products.

Proper  support  of  heat  reclaim  valves  is  essential.  Concentrated 

stresses  resulting  from  thermal  expansion  or  compressor  vibra-

tions can cause fatigue failure of tubing, elbows and valve fittings. 

Fatigue failures can also result from vapor propelled liquid slug-

ging, and condensation induced shock. The use of piping brackets 

close to each of the three way valve fittings is recommended.

Suction­

Reclaim

Con­den­ser­

Compr­essor­

Dischar­ge

Nor­mal

Con­den­ser­

1/4” SAE

A

B

D

C

E

G

Option­al 1/2” 

Con­duit Boss

J

F

Figure 2

H

Compr­essor­

Dischar­ge

 

Suction­

Reclaim

Con­den­ser­

Bleed Hole

Figure 1

“B” TYPE

RECLAIM CONDENSER

PUMP OUT

DIMENSIONS – In­ches

Содержание 10G711B

Страница 1: ...tructions 3 Way Valves CONTENTS B5D 8D 12D 16D 3 Way Heat Reclaim Valves 2 8D SC 12D SC 16D SC 3 Way Split Condenser Valves 5 10G79B 10G711B 10G711C 3 Way Hot Gas Defrost Valves 6 180 Solenoid Pilot Control 8 General Information 11 Replacement Parts Kits 12 ...

Страница 2: ... there is no high to low side bleed and resulting ca pac i ty loss with the system in the reclaim mode Valves using the MKC 1 coil may be used on fluids or gases where the temperature does not exceed 240 F while the valve ambient is 120 F The coil is Underwriters Laboratory Class F rated TYPES B5D 8D 12D 16D 3 WAY HEAT RECLAIM VALVES Bulletin 30 21 April 2007 supersedes Bulletin 30 21 June 2001 an...

Страница 3: ...ay coil is en er gized This al lows the heat ing to control the 3 Way Heat Re claim Valve op er a tion When the pump down control is de energized the normally closed con tact is closed This by pass es the heat ing to en er gize the coil and shut off the valve s bleed to suction B ts ts Reclaim Condenser Suction Normal Condenser Discharge Relay Closed Open Line Heating Thermostat Transformer Option...

Страница 4: ...e 4 This check valve required if lowest operating ambient temperature is lower than evaporator temperature Restrictor 2449 004 may be required to control pump out rate on inactive condenser Pilot suction line must be open to common suction whether or not Heat Reclaim Coil is installed at time of installation and regardless of Heat Reclaim Valve model type Proper support of heat reclaim valves is e...

Страница 5: ...ntial across the piston moves the piston seat assembly up to close the upper Condenser B port We use a solid piston ring on the piston thereby elimi nating high to low side bleed around the piston When the upper pilot port opens Condenser B is pumped out through a small bleed hole in the piston When Condenser B has been pumped out and reduced to suction pressure all flow ceases thus eliminating hi...

Страница 6: ...2 1 8 8 18 9 53 5 47 5 47 3 50 5 44 1 25 Suction A Pilot Valve Piston Upper Port Lower Port Plate Compressor Discharge Condenser B Summer Condenser A Summer Winter B C D E G H F Figure 7 Seat Disc Optional 1 2 Conduit Boss 1 64 TYPES 10G79B 10G711B 10G711C 3 WAY HOT GAS DEFROST VALVES D 4 95 4 95 2 89 1 56 Coil Removal B C B A 10 62 3 44 7 8 3 95 1 04 10G711C A Figure 6 shows a piping schematic to...

Страница 7: ...o the body from the top Push down on the pushrod q to re align if nec es sary 2 Install the bottom locknut R and tighten with a pipe wrench or torque wrench to 50 60 foot pounds torque This must be leak tight Do not over tight en 3 From the top of the body assembly Q install 10G79B 10G711B piston T in body bore compress the pis ton ring and slide the piston T all the way into the bore 10G711C seat...

Страница 8: ...ssures tend to establish a point of equilibrium to maintain a constant superheat at the outlet of the evaporator However when an abnormal pressure is introduced which upsets the equilibrium another effect may be accomplished The principle upon which the 180 Solenoid Pilot Control influences the expansion valve action is by the creation of a pressure under the valve diaphragm which is higher than t...

Страница 9: ...and sen sor bulb be installed within the refrigerated space so the bulb tem perature will be the same as the evaporator during the off cycle Not only will this prevent compressor flood back on start up but it will help insure a liquid line pressure higher than the bulb pressure to keep the expansion valve closed tight during the off cycle Comfort Cooling Application Intermittent Operation In certa...

Страница 10: ...ll a pressure gauge by means of a T fitting in the external equalizer connection to the thermostatic expansion valve as shown in Figure 12 By successively opening and closing the circuit to the Pilot Control only with the refrigeration system and circulating fans or pumps in operation variations approximating condensing pres sure and suction pressure should be observed on this gauge A If pressure ...

Страница 11: ...cal specifica tions of the coil to be sure that they correspond to the available electrical service See page 3 for typical wiring schematics for single compressor systems The 1 2 BX conduit connection of junction box on the coil of Heat Reclaim Valves may be ro tat ed to any po si tion by loos en ing the coil screw Valves with four wire dual volt age coil have a wiring di a gram decal see diagram ...

Страница 12: ...Valve Assembly 16D 12 03 and after KS 16DP A 16D SC KS 16DP SC 16D SC 12 03 and after KS 16DP SC A Hot Gas Defrost Valves 10G79B KS 10G 1 Enclosing Tube Gasket 2 Pilot Assembly Gaskets 1 Plunger Assembly 1 Pushrod 1 Seat Assembly 1 Piston Assembly 1 Valve Spring 10G711A B C 10G713 Pilot Assembly 2 Pilot Assembly Gaskets 1 Pilot Valve Assembly 1 Coil Housing Screw 1 Bottom Plate 10G B KS 10GP B 10G...

Отзывы: